Piping installation
Installer and user reference guide
98
(a)
ONLY required for RYYQ8~20 models, NOT for RXYQ8~54 and RYYQ22~54.
Parameter C:
Model
(b)
If N
8 HP
N≥4
10 HP
N≥5
12 HP
N≥6
14 HP
N≥7
16 HP
N≥8
18 HP
N≥9
20 HP
N≥10
(a)
Total CR = Total indoor unit capacity connection ratio
(b)
Number of VRV DX and RA DX indoor units connected to the outdoor unit.
Parameter C – Example with multiple outdoor units:
500
8 HP
12 HP
200
300
#
1
Determine the connection ratio:
Total outdoor unit capacity class = 500
Total indoor unit capacity class = 550
=> CR≥100%
2
Determine parameter C:
N=5
8 HP: N≥4 => C1=N×0.1=5×0.1 kg
12 HP: N<6 => C2=0 kg
=> C=C1+C2=0.5 kg
Metric piping. When using metric piping, replace the weight factors in the formula
by the ones from the following table:
Inch piping
Piping
Ø6.4 mm
Ø9.5 mm
Ø12.7 mm
Ø15.9 mm
Ø19.1 mm
Ø22.2 mm
(a)
CR
≥100%
Then C
C=N×0.1 kg
550
125
125
125 125
50
Action
Weight factor
0.022
0.059
0.12
0.18
0.26
0.37
(b)
If N
Then C
N<4
C=0 kg
N<5
N<6
N<7
N<8
N<9
N<10
Metric piping
Piping
Weight factor
Ø6 mm
Ø10 mm
Ø12 mm
Ø15 mm
Ø16 mm
Ø18 mm
Ø22 mm
4P546228-1C – 2021.11
(a)
CR
<100%
C=0 kg
0.018
0.065
0.097
0.16
0.18
0.24
0.35
RYYQ+RYMQ+RXYQ
VRV IV+ heat pump