Connection ratio requirements. When selecting indoor units, the connection ratio
must comply with the following requirements. For more information, see the
technical engineering data.
Other combinations than those mentioned in the table are not allowed.
Indoor units Total CR
VRV DX
50~130%
VRV DX +
80~130%
RA DX
RA DX
80~130%
VRV DX + LT
50~130%
Hydrobox
VRV DX +
50~110%
AHU
AHU
90~110%
(a)
Total CR = Total indoor unit capacity connection ratio
(b)
CR per type = Allowable capacity connection ratio per indoor unit type
(a)
VRV DX
RA DX
50~130%
0~130%
0~130%
80~130%
50~130%
50~110%
17
Piping installation
|
(b)
CR per type
LT Hydrobox
0~80%
Installer and user reference guide
AHU
0~60%
90~110%