18.1.5 About electrical compliance

RYYQ+RYMQ+RXYQ
VRV IV+ heat pump
4P546228-1C – 2021.11
a
a Knockout hole
b Burr
c Remove burrs
d If there are any possibilities that small animals enter the system through the
knockout holes, close the holes with packing materials (to be prepared on-site)
This equipment complies with:
EN/IEC 61000‑3‑11 provided that the system impedance Z
to Z
at the interface point between the user's supply and the public system.
max
-
EN/IEC 61000‑3‑11 = European/International Technical Standard setting the
limits for voltage changes, voltage fluctuations and flicker in public low-voltage
supply systems for equipment with rated current ≤75 A.
-
It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the
equipment is connected ONLY to a supply with a system impedance Z
than or equal to Z
max
EN/IEC 61000‑3‑12 provided that the short-circuit power S
equal to the minimum S
and the public system.
-
EN/IEC 61000‑3‑12 = European/International Technical Standard setting the
limits for harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and ≤75 A per phase.
-
It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the
equipment is connected ONLY to a supply with a short-circuit power S
than or equal to the minimum S
Model
RYYQ8/RYMQ8/RXYQ8
RYYQ10/RYMQ10/RXYQ10
RYYQ12/RYMQ12/RXYQ12
RYYQ14/RYMQ14/RXYQ14
RYYQ16/RYMQ16/RXYQ16
RYYQ18/RYMQ18/RXYQ18
RYYQ20/RYMQ20/RXYQ20
RYYQ22/RXYQ22
RYYQ24/RXYQ24
RYYQ26/RXYQ26
RYYQ28/RXYQ28
RYYQ30/RXYQ30
b
c
.
value at the interface point between the user's supply
sc
value.
sc
Z
18
Electrical installation
|
d
is less than or equal
sys
is greater than or
sc
(Ω)
Minimum S
max
(kVA)
4050
5535
6038
6793
7547
8805
9812
11573
11597
12831
13585
14843
Installer and user reference guide
less
sys
greater
sc
value
sc
113