Daikin VRV IV+ RYYQ8U7Y1B Series Installer And User Manual page 133

Hide thumbs Also See for VRV IV+ RYYQ8U7Y1B Series:
Table of Contents

Advertisement

RYYQ+RYMQ+RXYQ
VRV IV+ heat pump
4P546228-1C – 2021.11
[2‑25]
1
2 (default)
3
[2‑26]
Low noise operation start time.
This setting is used in conjunction with setting [2‑22].
[2‑26]
1
2 (default)
3
[2‑27]
Low noise operation stop time.
This setting is used in conjunction with setting [2‑22].
[2‑27]
1
2
3 (default)
[2‑30]
Power consumption limitation level (step  1) via the external control adaptor
(DTA104A61/62).
If the system needs to be running under power consumption limitation conditions
when an external signal is sent to the unit, this setting defines the level power
consumption limitation that will be applied for step 1. The level is according to the
table.
[2‑30]
1
2
3 (default)
4
5
6
7
8
[2‑31]
Power consumption limitation level (step  2) via the external control adaptor
(DTA104A61/62).
Description
Level 1
Level 3<Level 2<Level 1
Level 2
Level 3
Start time automatic low noise operation
(approximately)
Stop time automatic low noise operation
(approximately)
Power consumption limitation (approximately)
19
Configuration
|
20h00
22h00
24h00
6h00
7h00
8h00
60%
65%
70%
75%
80%
85%
90%
95%
Installer and user reference guide
133