Daikin VRV IV+ RYYQ8U7Y1B Series Installer And User Manual page 139

Hide thumbs Also See for VRV IV+ RYYQ8U7Y1B Series:
Table of Contents

Advertisement

RYYQ+RYMQ+RXYQ
VRV IV+ heat pump
4P546228-1C – 2021.11
Quick
Overshoot (during heating operation) or undershoot (during cooling operation) is
allowed compared to the requested refrigerant temperature, in order to achieve
the required room temperature very fast. The overshoot is allowed from the start
up moment.
In case of cooling operation the evaporating temperature is allowed to go down
to 6°C on temporary base depending on the situation.
In case of heating operation the condense temperature is allowed to go up to
46°C on temporary base depending on the situation.
When the request from the indoor units becomes more moderate, the system
will eventually go to the steady state condition which is defined by the operation
method above.
To activate this in...
Cooling operation
Heating operation
Mild
Overshoot (during heating operation) or undershoot (during cooling operation) is
allowed compared to the requested refrigerant temperature, in order to achieve
the required room temperature very fast. The overshoot is not allowed from the
start up moment. The start up occurs under the condition which is defined by the
operation mode above.
In case of cooling operation the evaporating temperature is allowed to go down
to 6°C on temporary base depending on the situation.
In case of heating operation the condense temperature is allowed to go up to
46°C on temporary base depending on the situation.
When the request from the indoor units becomes more moderate, the system
will eventually go to the steady state condition which is defined by the operation
method above.
The start up condition is different from the powerful and quick comfort setting.
To activate this in...
Cooling operation
Heating operation
Eco
The original refrigerant temperature target, which is defined by the operation
method (see above) is kept without any correction, unless for protection control.
19
|
Change...
[2‑81]=2.
This setting is used in conjunction with
setting [2‑8].
[2‑82]=2.
This setting is used in conjunction with
setting [2‑9].
Change...
[2‑81]=1.
This setting is used in conjunction with
setting [2‑8].
[2‑82]=1.
This setting is used in conjunction with
setting [2‑9].
Installer and user reference guide
Configuration
139