Application guidelines
Installer reference guide
44
f
3
System with hydraulic separator for both zones:
For this system, a direct pump is required for the additional zone.
f
A Additional leaving water temperature zone
B Room 1
C Room 2
D Main leaving water temperature zone
E Room 3
a Heat pump convectors (+ controllers)
b Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat)
c Mixing valve station
d Pressure regulating valve (field supply)
e Safety thermostat (field supply)
f Bizone kit control box (EKMIKPOA)
g Bypass valve
h Hydraulic separator (balancing bottle)
i Direct pump (for additional zone) (e.g. unmixed pump group EKMIKHUA)
INFORMATION
A pressure regulating valve should be implemented before the mixing valve station.
This is to guarantee the correct water flow balance between the main leaving water
temperature zone and the additional leaving water temperature zone in relation to
the required capacity of both water temperature zones.
B
C
A
a
a
D
E
e
d
h
c
B
C
A
h
i
a
D
E
e
d
c
EPRA14~18DAV3+W1 + ETVH/X16S18+23EA6V+9W
b
g
a
b
g
Daikin Altherma 3 H HT F
4P644737-1 – 2021.02