15 Disposal

In this chapter

15.1 To recover refrigerant

EPRA14~18DAV3+W1 + ETVH/X16S18+23EA6V+9W
Daikin Altherma 3 H HT F
4P644737-1 – 2021.02
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
15.1
To recover refrigerant ............................................................................................................................................................ 249
15.1.1
To manually open the electronic expansion valves............................................................................................... 250
15.1.2
Recovery mode....................................................................................................................................................... 251
When disposing of the outdoor unit, you need to recover its refrigerant.
Use the service port (a) to recover refrigerant.
Make sure the valves (Y1E, Y3E, Y2S, Y3S, Y4S) are open. If they are not open
during refrigerant recovery, refrigerant remains trapped in the unit.
Y2S
Y3S
Y4S
a
a Service port 5/16" flare
Y1E Electronic expansion valve (main)
Y3E Electronic expansion valve (injection)
Y2S Solenoid valve (low pressure bypass)
Y3S Solenoid valve (hot gas bypass)
Y4S Solenoid valve (liquid injection)
To recover refrigerant when power is ON
WARNING
Rotating fan. Before powering ON or servicing the outdoor unit, make sure that the
discharge grille covers the fan as protection against a rotating fan. See:
"7.3.6 To install the discharge
"7.3.7 To remove the discharge grille, and put the grille in safety
1 Make sure the unit is not running.
2 Activate the recovery mode (see
Result: The unit opens the valves (Y*).
Y1E
Y3E
4
grille" [
 75]
"15.1.2 Recovery
15
Disposal
|
4
position" [
 76]
4
mode" [
 251]).