Field settings table
Breadcrumb Field code
Setting name
9.I
[6-09]
--
9.I
[6-0A]
What is the desired comfort storage temperature?
9.I
[6-0B]
What is the desired eco storage temperature?
9.I
[6-0C]
What is the desired reheat temperature?
9.I
[6-0D]
What is the desired DHW production type?
9.I
[6-0E]
What is the maximum temperature setpoint?
9.I
[7-00]
Domestic hot water booster heater overshoot temperature.
9.I
[7-01]
Domestic hot water booster heater hysteresis.
9.I
[7-02]
How many leaving water temperature zones are there?
9.I
[7-03]
--
9.I
[7-04]
--
9.I
[7-05]
Boiler efficiency
9.I
[7-06]
Compressor forced OFF
9.I
[7-07]
BBR16 activation (#)
9.I
[7-09]
--
9.I
[7-0A]
Additional zone fixed pump PWM, in case a bizone kit is installed.
9.I
[7-0B]
Main zone fixed pump PWM, in case a bizone kit is installed.
9.I
[7-0C]
Time needed by the mixing valve to turn from one side to the other, in case a
bizone kit is installed.
9.I
[8-00]
Minimum running time for domestic hot water operation.
9.I
[8-01]
Maximum running time for domestic hot water operation.
9.I
[8-02]
Anti-recycling time.
9.I
[8-03]
Booster heater delay timer.
9.I
[8-04]
Additional running time for the maximum running time.
9.I
[8-05]
Allow modulation of the LWT to control the room temp?
9.I
[8-06]
Leaving water temperature maximum modulation.
9.I
[8-07]
What is the desired comfort main LWT in cooling?
9.I
[8-08]
What is the desired eco main LWT in cooling?
9.I
[8-09]
What is the desired comfort main LWT in heating?
9.I
[8-0A]
What is the desired eco main LWT in heating?
9.I
[8-0B]
--
9.I
[8-0C]
--
9.I
[8-0D]
--
9.I
[9-00]
What is the maximum desired LWT for main zone in heating?
9.I
[9-01]
What is the mimimum desired LWT for main zone in heating?
9.I
[9-02]
What is the maximum desired LWT for main zone in cooling?
9.I
[9-03]
What is the mimimum desired LWT for main zone in cooling?
9.I
[9-04]
Leaving water temperature overshoot temperature.
9.I
[9-05]
What is the mimimum desired LWT for add. zone in heating?
9.I
[9-06]
What is the maximum desired LWT for add. zone in heating?
9.I
[9-07]
What is the mimimum desired LWT for add. zone in cooling?
9.I
[9-08]
What is the maximum desired LWT for add. zone in cooling?
9.I
[9-09]
What is the allowed LWT undershoot during cooling start-up?
4P644734-1 - 2021.02
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(#) Only applicable in Swedish language.
Range, step
Default value
0
30~[6-0E]°C, step: 1°C
60°C
30~min(50, [6-0E])°C, step: 1°C
45°C
30~min(50, [6-0E])°C, step: 1°C
45°C
0: Reheat only
1: Reheat + sched.
2: Scheduled only
(*3) [E-07]=0 or 7:
40~ 60°C, step: 1°C
60°C
(*3) [E-07]=3 or 5 or 8:
40~80°C, step: 1°C
80°C
(*4) : 40~65°C, step: 1°C
65°C
0~4°C, step: 1°C
0°C
2~40°C, step: 1°C
2°C
0: 1 LWT zone
1: 2 LWT zones
2.5
0
0: Very high
1: High
2: Medium
3: Low
4: Very low
0: Disabled
1: Enabled
0: Disabled
1: Enabled
20
20~95%, step 5%
95%
20~95%, step 5%
95%
20~300 seconds, step 5 sec
125 seconds
0~20 min, step 1 min
1 min
5~95 min, step: 5 min
30 min
0~10 hour, step: 0,5 hour
0,5 hour [E-07]=1
3 hour [E-07]≠1
20~95 min, step: 5 min
50 min
0~95 min, step: 5 min
95 min
0: No
1: Yes
0~10°C, step: 1°C
5°C
[9-03]~[9-02], step: 1°C
18°C
[9-03]~[9-02], step: 1°C
20°C
[9-01]~[9-00], step: 1°C
35°C
[9-01]~[9-00], step: 1°C
33°C
13
10
16
[2-0C]=2:
37~70, step: 1°C
70°C
37~68, step: 1°C (*7)
68°C
[2-0C]≠2:
37~55, step: 1°C
55°C
15~37°C, step: 1°C
25°C
18~22°C, step: 1°C
22°C
5~18°C, step: 1°C
7°C
1~4°C, step: 1°C
1°C
15~37°C, step: 1°C
25°C
[2-0D]=2:
37~70, step: 1°C
70°C
37~68, step 1°C (*7)
68°C
[2-0D]≠2:
37~55, step: 1°C
55°C
5~18°C, step: 1°C
7°C
18~22°C, step: 1°C
22°C
1~18°C, step: 1°C
18°C
Installer setting at variance with
default value
Date
Value
(*1) *6V_(*2) *9W_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*_(*7) *SU*