Code
[5.3]
[6-0B]
Reheat setpoint
Desired reheat tank temperature, used:
in Schedule + reheat mode, during reheat mode: the guaranteed minimum
tank temperature is set by the Reheat setpoint minus the reheat hysteresis.
If the tank temperature drops below this value, the tank is heated up.
during storage comfort, to prioritize the domestic hot water preparation. When
the tank temperature rises above this value, domestic hot water preparation and
space heating/cooling are executed sequentially.
#
Code
[5.4]
[6-0C]
Schedule
You can set the tank temperature schedule using the schedule screen. For more
information about this screen, see
Heat up mode
The domestic hot water can be prepared in 3 different ways. They differ from each
other by the way the desired tank temperature is set and how the unit acts upon it.
#
Code
[5.6]
[6-0D]
See the operation manual for more details.
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by periodically
heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
Description
Eco setpoint:
30°C~min(50,[6‑0E])°C
Description
Reheat setpoint:
30°C~min(50,[6‑0E])°C
"10.3.7 Schedule screen:
Description
Heat up mode:
0: Reheat
only: Only reheat operation is
allowed.
1: Schedule + reheat: The domestic hot
water tank is heated according to a schedule
and between the scheduled heat up cycles,
reheat operation is allowed.
2: Schedule only: The domestic hot water
tank can ONLY be heated according to a
schedule.
EPRA14~18DAV3+W1 + ETVH/X16S18+23EA6V+9W
4
Example" [
 138].
Daikin Altherma 3 H HT F