EPRA14~18DAV3+W1 + ETBH/X16EF6V+9W
Daikin Altherma 3 H HT W
4P644736-1 – 2021.02
In case of normal kWh rate power supply
Interconnection cable
(= main power supply)
—
A
B
C
B
X2M
X1M
A1P
a Interconnection cable (=main power supply)
In case of preferential kWh rate power supply
Interconnection cable
(= main power supply)
Normal kWh rate
power supply
Preferential kWh rate
power supply contact
[9.8] Benefit kWh power supply
Connect X11Y to X11YB.
Wires: (3+GND)×1.5 mm²
A
a
1 2 3
C
X11Y
X11YA
X11YB
1 2 3
X1M
X1A
a
Wires: (3+GND)×1.5 mm²
Wires: 1N
Maximum running current: 6.3 A
Wires: 2×(0.75~1.25 mm²)
Maximum length: 50 m.
Preferential kWh rate power supply contact:
16 V DC detection (voltage supplied by PCB). The
voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.
9
Electrical installation
|
X2M
A1P
Installer reference guide
111