RUGGEDCOM RS1600F
Installation Guide
Technical Specifications
The following sections provide important technical specifications related to the device and available modules:
•
Section 4.1, "Power Supply Specifications"
•
Section 4.2, "Failsafe Relay Specifications"
•
Section 4.3, "Fiber Optic Ethernet Port Specifications"
•
Section 4.4, "Operating Environment"
•
Section 4.5, "Mechanical Specifications"
Section 4.1
Power Supply Specifications
Power Supply Type
12–24 VDC
24 VDC
48 VDC
d
HI (125/250 VDC)
d
HI (110/230 VAC)
a
(F) denotes fast-acting fuse
b
(T) denotes time-delay fuse.
c
Power consumption varies based on configuration. 10/100Base-TX ports consume roughly 1 W less than fiber optic ports.
d
Same power supply for both AC and DC.
Section 4.2
Failsafe Relay Specifications
Power Supply Specifications
Input Range
Minimum
Maximum
10 VDC
36 VDC
18 VDC
36 VDC
36 VDC
59 VDC
88 VDC
300 VDC
85 VAC
265 VAC
Voltage
30 VAC
30 VDC
80 VDC
Internal Fuse
Isolation
ab
Rating
6.3 A(F)
1.5 kVDC
5 A(F)
1.5 kVDC
2 A(T)
1.5 kVDC
2 A(T)
5.5 kVDC
2 A(T)
4 kVAC
Current
0.3 A
1 A
0.3 A
Chapter 4
Technical Specifications
Maximum Power
c
Consumption
34 W
17