Function Settings - Mitsubishi Electric LGH-15RVX3-E Installation Instructions Manual

Lossnay heat recovery ventilator
Hide thumbs Also See for LGH-15RVX3-E:
Table of Contents

Advertisement

5. Function settings

Address setting is required when connecting to City Multi and
MELANS.
Setting the address
Use the following procedure when setting the address for dedicated
Lossnay.
(The method in determining the addresses will depend on the existing
system. Refer to the appropriate technical documents for details.)
(1) Remove the control box cover.
(2) Turn the address setting switch on the circuit board.
• SW12 indicates the tens digit and SW11 indicates the ones digit.
• The factory setting is "00".
Address setting switch
SW12 (Tens digit)
* When the address number has been changed, the data in the
memory is automatically reset.
Changing the function selection
switches (SW-2, 5 and 6)
Set the selection switches (SW-2 and 5) to perform the appropriate
function.
* All function except "Trial operation" and "Auto fan speed setting
without Lossnay or M-NET remote controller" can be set also from
the remote controller (PZ-62DR-EA/EB). If the function is switched
later using the remote controller, it operates according to the setting
on the remote controller.
(SW2)
OFF
ON
Trial operation
1
No. 28
Pulse input setting
2
No. 9
Delay start setting for air conditioner starting
3
No. 6
Indoor negative pressure setting
4
No. 7
Indoor positive pressure setting
5
No. 64
Fan speed for air volume "High" setting
6
No. 65
Fan speed for air volume "Low" setting
7
No. 5
Automatic recovery setting after power interruption
8
No. 70
Dx-coil unit connection selecting
9
N/A
10
(SW5)
OFF
ON
No. 12
Monitor output setting
1
2
No. 17
Exhaust fan setting during air conditioner defrosting
3
4
No. 71
Selection of the operation mode from "Temp. priority mode" or "Fan speed priority mode" with DX-coil unit
5
6
No. 66
CO
sensor or BMS setting
2
7
8
When connecting the CO
9
N/A
10
Address setting switch
SW11 (Ones digit)
sensor, Auto fan speed setting without Lossnay remote controller or M-NET system controller
2
Change the function settings from the
remote controller PZ-62DR-EA/EB.
Please refer to the Instruction book of PZ-62DR-EA/EB for how to set
the function settings.
DIP-SW6 is to identify the model for circuit board. When
replacing to new circuit board, set the same setting as old
one.
(SW6)
LGH-15RVX3-E
LGH-25RVX3-E
LGH-35RVX3-E
LGH-50RVX3-E
LGH-65RVX3-E
LGH-80RVX3-E
LGH-100RVX3-E
LGH-160RVX3-E
LGH-200RVX3-E
* Do not change from factory setting. If changed, please set as
factory setting.
Eng-18
2303N22HHZA0013
SW6-1 SW6-2 SW6-3 SW6-4 SW6-5 SW6-6
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF