No.36
Outdoor temperature display setting
Set to display outdoor temperature detected by Lossnay unit
thermistor.
This function is N/A from Lossnay unit DIP-SW.
This function is available only when "Sensor value" is set to "Yes"
(Display) by the remote controller PZ-62DR-EA/EB.
DIP-SW
PZ-62DR-EA/EB Setting
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
36
-
-
No.37
Indoor temperature display setting
Set to display indoor temperature detected by Lossnay unit thermistor.
This function is N/A from Lossnay unit DIP-SW.
This function is available only when "Sensor value" is set to "Yes"
(Display) by the remote controller PZ-62DR-EA/EB.
DIP-SW
PZ-62DR-EA/EB Setting
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
37
-
-
No.38
CO
concentration display setting
2
Set to display CO
concentration when the CO
2
PZ-70CSW-E) is used.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-EA/EB Setting
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
38
-
-
- This function is available only when "Sensor value" is set to "Yes"
(Display) by the remote controller PZ-62DR-EA/EB.
- When displaying CO
concentration, supply air temperature cannot
2
be displayed simultaneously.
- CO
concentration display shows the value detected by a CO
2
sensor connected to Lossnay unit. The value may differ from the
actual indoor CO
concentration. This function cannot be used as a
2
measuring instrument.
- The value may significantly differ from the actual indoor CO
concentration for approx. 15 minutes after starting operation.
- When 3rd party's CO
sensor is connected, CO
2
displayed on PZ-62DR-EA/EB screen.
No.39
Calculated supply air temperature display
setting
Set to display calculated supply air temperature or not.
This function is N/A from Lossnay unit DIP-SW.
In addition, this function is available only when "Sensor value" is set to
"Yes"(Display) by the remote controller PZ-62DR-EA/EB.
CO
concentration and supply air temperature can not be displayed at
2
the same time.
DIP-SW
PZ-62DR-EA/EB Setting
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
39
-
-
- CO
concentration and supply air temperature can not be displayed
2
at the same time.
Outdoor temperature
check
display
0
N/A
1
Available on the screen
(Factory setting)
of PZ-62DR-EA/EB
Indoor temperature
check
display
0
N/A
Available on the screen
1
(Factory setting)
of PZ-62DR-EA/EB
sensor (PZ-70CSD-E,
2
CO
concentration
2
check
display
0
N/A
1
Available on the screen
(Factory setting)
of PZ-62DR-EA/EB
2
concentration is not
2
Calculated supply air
check
temperature display
0
N/A
(Factory setting)
Available on the screen
1
of PZ-62DR-EA/EB
No.40, 41
Set the 10 digit of temperature exchange efficiency which is used to
calculate supply air temperature.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
-
N/A
-
-
-
-
-
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
N/A
-
-
-
-
-
-
No.42
Outdoor temperature correction
Set the correction for the outdoor temperature displayed on the
PZ-62DR-EA/EB screen by function
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
-
2
-
-
N/A
-
-
-
-
-
-
-
-
Eng-24
Temperature exchange efficiency
setting
PZ-62DR-EA/EB Setting
10 digit of temperature
check
exchange efficiency
Function No. Setting Data
-
0
0
-
1
1
-
2
2
-
3
3
-
4
4
-
40
5
5
-
6
6
7
-
7
(Factory setting)
-
8
8
-
9
9
PZ-62DR-EA/EB Setting
1 digit of temperature
check
exchange efficiency
Function No. Setting Data
0
-
0
(Factory setting)
-
1
1
-
2
2
-
3
3
-
41
4
4
-
5
5
-
6
6
-
7
7
-
8
8
-
9
9
.
No. 36
PZ-62DR-EA/EB Setting
The correction to
check
thermistor detection
Function No. Setting Data
-
0
-7 K (-7 °C)
-
1
-6 K (-6 °C)
-
2
-5 K (-5 °C)
-
3
-4 K (-4 °C)
-
4
-3 K (-3 °C)
-
5
-2 K (-2 °C)
-
6
-1 K (-1 °C)
7
-
42
0 K (0 °C)
(Factory setting)
-
8
+1 K (+1 °C)
-
9
+2 K (+2 °C)
-
10
+3 K (+3 °C)
-
11
+4 K (+4 °C)
-
12
+5 K (+5 °C)
-
13
+6 K (+6 °C)
-
14
+7 K (+7 °C)
2303N22HHZA0013