Pump - Head Only; Pump - Complete - Main Eco Compact System 15 Installation And Service Manual

High efficiency wall hung condensing gas boiler
Table of Contents

Advertisement

Fig.55
Remove pump head only
Fig.56
Remove pump
Warning
Ensure that both flue test point plugs are in place after checking
combustion.
9.3.9

Pump - head only

To remove the pump head only.
1. Drain the boiler primary circuit and disconnect the electrical plug from
the pump
2. Remove the socket head screws securing the pump head to the body
and draw the head away.
3. Fit the new pump head and reassemble in reverse order.
PN-0000380
9.3.10

Pump - complete

Warning
Take precautions to protect other components from water damage
when removing the pump and auto air vent.
1. Hinge the control box down.
2. Close the flow and return isolation taps and drain the boiler primary
circuit.
3. Disconnect the electrical plugs from the pump motor.
4. Prise off the securing clip that is holding the pump return pipe in
position. Pull away the pipe.
5. Pull out the securing clip that is holding the pump body to the
hydraulic inlet assembly.
6. Prise off the securing clip and disconnect the braided hose from the
pump body, taking care as water may still be in the hose.
7. Remove the screws securing the pump to the boiler bottom panel.
PN-0000379
8. The pump should now be able to be remove.
9. Pull out the securing clip and remove the automatic air vent,
transfering it to the new pump body.
10. Examine all 'O' ring seals, replace if necessary and reassemble in
reverse order.
9 Maintenance