2. General Data
Indoor Unit Type
Model
Indoor Unit Power Supply
Sound Pressure Level
(Overall A Scale) (Hi2/Hi/Me/Lo)
Cabinet Color
Outer Dimensions
Height
Width
Depth
Net Weight
Refrigerant
Indoor Fan
Air Flow Rate
(Hi2/Hi/Me/Lo)
Motor
Connections
Refrigerant Piping
Liquid Line
Gas Line
Condensate Drain
Approximate
Packing Measurement
NOTES:
1. The above cooling and heating capacities show the maximum capacities when the outdoor and indoor temperature are below condition.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature: 35
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Piping Length: 7.5 Meters
2. The sound pressure level is based on following conditions.
1 Meter Beneath the Unit and 1 Meter from Discharge Grille.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
TCI-20007-rev.1
RPC-1.5FSR
dB
37/35/31/28
mm
235
(in.)
(9-1/4)
mm
960
(in.)
(37-4/5)
mm
690
(in.)
(27-1/5)
kg
26
(lbs.)
(57)
3
15/13/11/9
m
/min.
(cfm)
(530/459/388/318)
W
50
mm
6.35
(in.)
(1/4)
mm
12.7
(in.)
(1/2)
VP20
3
0.23
m
o
o
27
C DB (80
F DB)
o
o
19.0
C WB (66.2
F WB)
o
o
C DB (95
F DB)
o
o
20
C DB (68
F DB)
o
o
7
C DB (45
F DB)
o
o
6
C WB (43
F WB)
Piping Lift: 0 Meter
Ceiling Type
RPC-2.0FSR
RPC-2.5FSR
AC 1, 220-240V/50Hz, 220V/60Hz
38/35/31/28
38/35/31/28
Neutral White
235
235
(9-1/4)
(9-1/4)
960
1270
(37-4/5)
(50)
690
690
(27-1/5)
(27-1/5)
27
(60)
(78)
R410A/R32
15/13/11/9
19/16.5/14/11.5
(530/459/388/318)
(671/582/494/406)
50
Flare-Nut Connection (with Flare Nuts)
6.35
9.52
(1/4)
(3/8)
12.7
15.88
(1/2)
(5/8)
VP20
VP20
0.23
0.31
GENERAL DATA
RPC-3.0FSR
40/37/33/29
235
(9-1/4)
1270
(50)
690
(27-1/5)
35
35
(78)
21/18.5/15.5/12.5
(741/653/547/441)
80
80
9.52
(3/8)
15.88
(5/8)
VP20
0.31
1-35