Hitachi RPC-1.5FSR Technical Catalogue page 44

Inverter-driven split system heat pump air conditioners set free fsr indoor units, indoor units, ceiling type
Table of Contents

Advertisement

FEATURES
Length of Wire Cable for Optional Wired Controller, Timer and Central Station
As the wired controllers, timer and central stations
do not include a controller cable, prepare one in
the field, or use PRC-5K, 10K or 15K.
2
Use the twist pair cable (1P-0.75mm
) as
transmission wire cable for prevention of the
malfunction (The total cable length is max. 500m).
When the total cable length is within 30m, other
types of cable (more than 0.3mm
2
) can be used.
Indoor Unit Quantity: 1
Wired Controller Quantity: 1
Application Function of Wired Controller
One indoor unit can be controlled by two optional
wired controllers separately mounted on the wall.
Indoor Unit Quantity: 1
Wired Controller Quantity: 2
One optional wired controller can start/stop up to
16 indoor units.
Indoor Unit Quantity: 16 (Maximum)
Wired Controller Quantity: 1
1-34
TCI-20007-rev.1