Motion Sensor Kit: Sor-Nep; Motion Sensor Kit: Sor-Nep - Hitachi RPC-1.5FSR Technical Catalogue

Inverter-driven split system heat pump air conditioners set free fsr indoor units, indoor units, ceiling type
Table of Contents

Advertisement

OPTIONAL ACCESSORIES
Item
Applicable Indoor Unit Model (RPC-**FSR)
Maximum Lift for Drain-Up
Power Source
Power Consumption
Drain Piping Connection
Diameter of
Field-processed Ref. Pipe
(Flare Nut Connection)
Applicable Refrigerant
Weight
Accessory
Protection Device
Antimicrobial Agent
Restrictions for Installation
Maintenance
NOTES:
1. Before installing the indoor unit, provide a hole (
refrigerant gas/liquid pipes and pipe for drain-up to mount the drain-up mechanism.
2. PVC Tube (VP25) must be used for the drain connection.
3. Lower the indoor unit 10mm when the drain-up mechanism is installed.
(In case of inclination beyond 10mm, it'll be water leakage or abnormal stoppage.)
4. Do not provide a trap or riser portion for the drain pipe. Install the pipe with a falling gradient of 1/25 ~
1/100.
5. Cover the drain pipe and refrigerant gas/liquid pipes with insulations in order to avoid dew condensation.
6. Do not take out and put in connectors frequently. Constant taking out and putting in can lead to a PCB
malfunction.
7. Install the indoor unit in a horizontal position only. An Inclined unit can result in water leakage or abnormal
stoppage.
8. Before shipment, the accessory drain-up pipe's height from the upper surface of the unit is set to 600 mm,
which can be lowered to 150 mm. If making the height lower, cut the pipe on site.
9. After installing the drain-up mechanism, sound of drain water flowing can be heard. This is the sound
made when the drain water is discharged and so there are no safety concerns.

8.2.3 Motion Sensor Kit: SOR-NEP

Refer to chapter 1.4.13 for details.
1-54
Model
DUPC-63K1
mm
W
A
Gas
mm
Liquid B
Drain Hose, Pipe for Drain-Up, Ref. Gas/Liquid Pipes for Upper Side of
Indoor Unit, Clamp, Insulation, Screws, Installation and Maintenance
Manual
Float Switch (for Alarm)
Silver-Ionic Antimicrobial Agent Using Dissoluble Glass
1. When viewed from the front, the position of drain-up pipe must be on
the right side of the indoor unit.
2. Ref. gas/liquid pipes (accessory) must be attached to the upper side
of the indoor unit.
Cleaning of Water tank: once a year
Cleaning of Pump: once a year
Cleaning of Float Switch: Once a year
Replacement Cycles for Antimicrobial Agent: At 10.000 hours (approx. 5
years)
For Ceiling Type
DUPC-71K1
1.5
2.0
600 (from the upper side of the indoor unit)
DC13V
4.2 or less
PVC Tube, VP25
12.7
12.7
6.35
6.35
R410A
3.5 kg
300 mm) for piping connection. Use the accessory
DUPC-160K1
2.5 to 6.0
15.88
9.52
TCI-20007-rev.1