You should be well-informed of the contents where WARNING is marked before carrying out the work. You should be careful where CAUTION is marked to carry out the work. You should be aware of where NOTICE is marked to carry out the work. HITROL CO., LTD.
Thus, if you regard it as Constant K, ΔC is decided only by l, the height of the substance you want to measure. Therefore, if you measure ΔC, you can identify the current position of Level. HITROL CO., LTD.
Ex-Proof (Ex d IIC T6, IP65) Ex-Proof (Ex d IIC T4, IP65) Ex-Proof (Ex d IIC T6, IP65) Ex-Proof (Ex d IIC T4, IP65) Wetted Parts Material SUS 304, 316L with TEFLON Process Connection PT 1”(M) Screw 50A JIS 10K RF FLANGE Housing ; Cable Entry AL. ; PF 3/4”(F) Accuracy Up to ±1% of F.S HITROL CO., LTD.
: material: 304,316L Weight 304,316L 304,316L with material : with TEFLON 304,316L, TEFLON TEFLON Weight material : Wire Probe Rod Probe Rod Probe Rod Probe Wire Probe with Ground Wire with Ground rod with Ground tube HITROL CO., LTD.
Page 6
Hexane, Liquid Butanol 17~18 Ammonia 16~25 Alcohol 16~31 Acetone Caustic soda 22~26 Ethanol Methano 32~33 Glycerin 47~68 Water Sulfuric acid Information about the relative dielectric constant can be downloaded from our website by accessing the Knowledge Base www.hitrol.com. HITROL CO., LTD.
(f). ■ If the tank has a mixer, install the probe at a safe distance from the mixer. ■ If the tank wall has a structure (ex. angle), use the probe with the ground tube (e) HITROL CO., LTD.
Page 8
■ If the tank structure is a sphere tank type, use the probe with the ground tube. (h) ■ If the probe is installed at the tank side, install the chamber. (i) ■ The ground tube should have ventholes at proper places. ( j) ( j) Vent holes HITROL CO., LTD.
Page 9
Nonconductive Tanks (Nonmetal tanks) When installing the probe in a nonconductive tank, the ground tube (rod) or ground wire should be used and grounded with a transmitter housing like in the figure below. HITROL CO., LTD.
ON/OFF the Full Range ADJ. (③) in the order of 6->5->4->3->2->1, and adjust it until the indicator points near 100%. [2] Set it at accurate 0% using Full Range ADJ. (④) for fine adjustment. (Span adjustment range: 40–4,000pF) HITROL CO., LTD.
■ Make sure that any O-ring or gasket is not damaged while opening or closing the cover of product. Make sure that it is not subject to any high impact while moving. If there is an atmosphere of explosive gas, do not open the cover of the product. HITROL CO., LTD.
Make sure to insert a washer if the terminal lug is removed from ground terminal and then re- connected. (Loosening prevention) External Grounding 4㎟ (4mmSQ) HEAD External HEAD External Grounding Grounding (WEATHER PROOF) (EX PROOF) HITROL CO., LTD.
- The product identification mark is attached onto the housing and shows the model name, serial number, working temperature, working pressure, and matters regarding output. The serial number is a unique manufacturing number for the identification of products. Weather-proof Version < > <Ex-proof Version> HITROL CO., LTD.
You can request A/S at our website or by contacting our headquarters. ■ Headquarters ․ Factory ․ Laboratory Contact Number ADDRESS: HITROL CO., LTD 141, Palhakgol-gil, Jori-eup, Paju-si, Gyeonggi-do, Korea T E L : 031-950-9700 (Headquarters & A/S) F A X : 031-943-5600 (Headquarters & A/S)