Software Settings Switch; Connection Procedure; Input Power; 115 Vac - Varifan ECS 3M User Manual

Hide thumbs Also See for ECS 3M:
Table of Contents

Advertisement

2.3.2 - Software Settings Switch

This switch is located at the rear of the control panel
faceplate and adjusts the following options.
OFF
ON
1
Fahrenheit
2
Settings locked
3
Stage 3 = Heat
4
Not used
Switch 1
Selects
display for the front panel.
Switch 2
Locks/unlocks user settings. All settings except
for main set point, record low, and record high
are locked when this switch is OFF.
Switch 3
Selects between a Heater or Fan control on
stage three of the control panel.
Switch 4
With or without a humidity probe, DIP switch #4
must be ON.

2.4 CONNECTION PROCEDURE

For connection procedures which follow see figures 1 to 3.

2.4.1 - Input power

Use a screwdriver to remove cable knock-outs for cabling
installation to the control panel.

2.4.1.1 - 115 VAC

Do not apply power to the control panel until all
connections have been completed!
Make certain that the line voltage selector switch is set
to 115 VAC. Connect the power cable to terminals 7 and 8
on the main (bottom) board and connect the ground wire to
terminal 9 on the main board .
www.monitrol.com
CHAPTER 2 - INSTALLATION
OFF
Celsius
Setting unlocked
Stage 3 = Fan
Relative Humidity
the
Fahrenheit
or
ON
Celsius
Page 11

Advertisement

Table of Contents
loading

Table of Contents