Connecting up
5.1 Safety when connecting up
Unsuitable cables or connectors
Risk of explosion in hazardous areas
• Only use connectors that meet the requirements of the relevant type of protection.
• If necessary, tighten the connector screw connections, device fastening screws, grounding
• Close unused cable openings for electrical connections.
• Check the cables for a tight fit after installation.
Lack of equipotential bonding
If there is no equipotential bonding in hazardous areas, there is a risk of explosion due to
equalizing current or ignition sparks.
• Ensure that equipotential bonding is available for the device.
Unprotected cable ends
There is a risk of explosion due to unprotected cable ends in hazardous areas.
• Protect unused cable ends according to IEC/EN 60079-14.
Improper installation of shielded cables
There is a risk of explosion due to equalizing currents between the hazardous area and the non-
hazardous area.
• Ground shielded cables that cross hazardous areas at one end only.
• Lay a potential equalization conductor when grounding at both ends.
Insufficient isolation of intrinsically safe and non-intrinsically safe circuits
Risk of explosion in hazardous areas
• When connecting intrinsically safe and non-intrinsically safe circuits, ensure that the
• Observe the device approvals applicable for your country.
44
WARNING
screws, etc. according to the specified torques.
WARNING
WARNING
WARNING
WARNING
galvanic isolation is performed properly in compliance with local regulations (e.g. IEC
60079-14).
Operating Instructions, 02/2023, C79000-G8976-C676-01