Technical specifications
Article number
Standards, approvals, certificates
CE mark
cULus
RCM (formerly C-TICK)
KC approval
EAC (formerly Gost-R)
Suitable for safety functions
Highest safety class achievable in safety mode
Performance level according to ISO 13849-1
SIL acc. to IEC 61508
Probability of failure (for service life of 20 years and
repair time of 100 hours)
Low demand mode: PFDavg in accord-
ance with SIL2
Low demand mode: PFDavg in accord-
ance with SIL3
High demand/continuous mode: PFH in
accordance with SIL2
High demand/continuous mode: PFH in
accordance with SIL3
Ambient conditions
Ambient temperature during operation
min.
max.
Ambient temperature during storage/transportation
min.
max.
Altitude during operation relating to sea level
Installation altitude above sea level, max.
Ambient air temperature-barometric pres-
sure-altitude
Configuration
Programming
Programming language
LAD
FBD
STL
SCL
GRAPH
86
6ES7615-4DF10-0AB0
Yes
Yes
Yes
Yes
Yes
Yes; e.g. emergency stop, acknowledgment button
PLd (PLe if exclusively F-CPU is used)
SIL 2 (SIL 3 if exclusively F-CPU is used)
< 14.00E-04
< 2.00E-05 PLd (if exclusively F-CPU is used)
< 14.00E-09
< 1.00E-09 (if exclusively F-CPU is used)
0 °C
55 °C
-40 °C; Long-term storage: -25 °C
70 °C; Long-term storage: +55 °C
4 000 m; Above an altitude of 2 000 m, the max. ambient tempera-
ture decreases by 7 °C every 1 000 m
Permissible air pressure: 620 hPa ... 1 060 hPa
Yes; incl. failsafe
Yes; incl. failsafe
Yes
Yes
Yes
6ES7615-7DF10-0AB0
SIMATIC Drive Controller
Equipment Manual, 11/2019, A5E46600370-AA

Advertisement