Terminal Block/
Connector
Notes:
1.
Total current drawn from the power supply by TB2, TB6 through TB9 and TB10 cannot exceed 3.0 A in standby or 6.0 A in an alarm
condition. The Control Panel provides a total of 4.4 A of power in standby and 7.4 A of power in alarm to be shared by all internal circuitry
and external provisions (24 V resettable and non-resettable).
2.
NFPA 72 Local, Proprietary, and Central Station systems require 24 hours of standby power followed by 5 minutes in alarm.
3.
NFPA 72 Auxiliary and Remote Station Systems require 24 hours of standby power followed by 5 minutes in alarm.
4.
Batteries installed in a system powered by an automatic starting engine generator need to provide at least 4 hours of standby power.
5.
Factory Mutual requires 90 hours of standby for deluge-preaction systems.
6.
Emergency voice/alarm communications systems require 2 hours of operation in the alarm condition. Due to the sporadic nature of voice
operation, however, NFPA 72 permits 15 minutes of operation at a maximum connected load to equal 2 hours of normal use.
7.
If the total exceeds 26 AH, the system requires a separate NFS-LBB, BB-100 or BB-200 battery enclosure for two larger capacity batteries.
8.
The following battery derating factors must be used for Canadian installations using NFS2-640 charger:
• For a 26 AH battery, use derating factor of 1.5
• For a 55 AH battery, use derating factor of 1.8
• For a 100 AH battery, use derating factor of 2.5
• For a 200 AH battery, use derating factor of 2.5
• For 26 AH batteries: maximum standby current cannot exceed 0.65A; maximum alarm current cannot exceed 6.75A.
9.
Internal Battery Charger on the CPS-24/E is rated for use with 18 AH to 200 AH batteries.
10. Accessories using the 5 VDC power connection must be located within 10 ft (3.658 m) of the FACP.
11. UL2610 Proprietary Burg requires 24 hours of standby power
8
Description
Table 2 NFS2-640Power Supply Wiring Connections (2 of 2)
Specifications
NFS2-640 UL Listing Document — P/N 52741LD:H9 5/19/2022