(a) on an open or short circuit
(b) on a ±50% change in resistance value from the End-of-Line resistor value
(c) on loss of communication with the device.
A tamper switch installed in the cabinet door will indicate a door tamper condition whenever the door is open. If the control panel indicates a Security
alarm, you can perform acknowledge, signal silence, and system reset from the control panel.
CAUTION: WIRING
!
DAMAGE CAN RESULT FROM INCORRECT WIRING CONNECTIONS.
General Security Requirements
The following security requirements must be met:
Shielded cable must be used on all input/output wiring associated with security functions.
SLC Loop Shielding (refer to the SLC Wiring Manual)
Security Module I/O Circuit Shielding - terminate the shield at earth ground at the junction box containing the module.
When employed as a Protected Premises Unit, the control panels cabinet door must be wired with an STS-1 Tamper Switch that is monitored by
the control panel
If the system has arming and disarming capability, a ring-back signal from the Central Station to the arming location is required. The ring-back
signal informs the Protected Premises Control Panel that the signal to arm/disarm has been received by the Central Station
An ACM-24AT point must be programmed as 'disable' for each security point or zone programmed, doing so allows for a manual bypass before
arming if the point or zone is in trouble
A duplicate control panel or sufficient spare parts should be made available so that the control panel can be brought back online within 30
minutes of any failure
There must be a sufficient number of ACM-24AT's installed on the control panel to show the status of each zone or point so that each zone or
point can be monitored Any ACM-24AT's or optional annunciators must be installed inside the protected area
A single control panel combines a Protected Premises Unit and Receiving Unit as a single unit, as such, it must be located in an area that is
monitored at all times
The Installer should be familiar with and follow the best practices set forth within ANSI/SIA CP-01 for troubleshooting and reduction in dispatch
calls
The loss of communication with the monitoring station shall be treated as an alarm condition by monitoring station personnel when the burglar
alarm system is in the armed state and as a trouble condition while the system is disarmed
Refer to the SLC Wiring Manual (51253) for additional information on required wiring sizes
NOTE: For Security applications the maximum number of points on a system must be limited to 1000 or less.
There are five software type IDs associated with security operation: A
M
. There is also one software function, Security Delay (SDEL). These software elements are essential to all aspects of security operation,
ONITOR
including Control-By-Event (CBE) programming. Devices with the type IDs A
the LCD or require state change acknowledgment. State changes in devices with these software types may be output at a printer.
NFS2-3030 Protected Premises Unit
47K
End-of-line
UL-listed,
normally-open
UL-listed,
normally-closed
Figure 13 Wiring Diagram for Proprietary Security Alarm
Wiring for Proprietary Security Alarm Applications
Typical wiring for proprietary security alarm applications with the FMM-1 module.
Note the following:
• The module is programmed with one of five type codes (see "General Security Requirements" on page 11).
• Supplementary use only applies to UL-listed systems.
• NAC devices used for security cannot be shared with fire NAC devices.
• Refer to the Device Compatibility Document for compatible NAC devices.
NOTE: If NAC devices are used, the audible pattern for a Security Alarm signal should be distinct from a Fire Alarm
All monitor modules used for security application must be installed in the control panel cabinet with STS-1 Security Tamper Switch.
NFS2-640 UL Listing Document — P/N 52741LD:H9 5/19/2022
CCESS
For security applications, program one or more monitor modules (listed for
security applications) with a security type code.
SLC
Note the following:
Channel A
•The module is programed as an ACCESS MONIITOR, AREA MONITOR,
or B
EQUIP MONITOR, SECURITY-L, or SYS MONITOR type code.
•Supplementary use applies to UL Systems only.
•NAC devices used for security cannot be shared with fire NAC devices.
•Refer to the Device Compatibility Document, document number 15378, for
compatible NAC devices.
•All monitor modules used for security applications must be installed in the
FMM-1
control panel with an STS-1 Security Tamper Switch.
M
alarm, A
M
ONITOR
REA
M
and E
CCESS
ONITOR
Proprietary Security Alarm Applications
, E
M
, S
ONITOR
QUIP
ONITOR
ECURITY
M
do not automatically display at
QUIP
ONITOR
-L, and S
YS
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier nfs2-640e

Table of Contents