1,2
SUP.T(LASER)
supervisory
SMOKE(DUCTL)
fire alarm
SUP T(DUCTL)
supervisory
SUP L(DUCTL)
supervisory
AIR REF
fire alarm
Note: A reference detector still functions as a smoke detector, but you should set the detector sensitivity level to the least sensitive level—AL:9 and
PA:9 Change Alarm and Pre-Alarm sensitivity. Refer to "Detector Sensitivity (in percent obscuration per foot)" on page 26 for a complete list of
detector sensitivity settings.
HEAT
fire alarm
HEAT+
fire alarm
HEAT(FIXED)
fire alarm
HEAT (ROR)
fire alarm
SMOKE ACCLIM
fire alarm
SMOKE(ACCLI+)
fire alarm
3
SMOKE(MULTI)
fire alarm
ASPIRATION
fire alarm
ASPIR (SUP)
supervisory
ASPIR. (PRE)
pre-alarm
ASPIR. (NON)
non-fire
ASPIR. (REF)
non-fire
Note: Aspiration detector (FAAST) programming requires 5 SLC addresses. When a device associated with a FAAST device is disabled locally, all
devices associated with that FAAST will be automatically disabled as well.
ACCLIMATE
ACCL (P SUP)
fire
ACCL+ (P SUP)
fire
For ACCL/ACCL+ detectors:
Note: Detectors programmed as ACCL (P SUP) or ACCL+ (P SUP), the heat element will latch and require a system reset to clear. The Photo
element will latch or track, depending on the ACCL (P SUP) latching setting.
1 Not suitable for Canadian applications
2 Requires approval of AHJ
3 CLIP mode only
4 LED representation of a CO alarm may be performed using an ACS annunciator
5 Photo element can be programmed as latching or tracking for all Photo/CO devices programmed as this type ID via VeriFire Tools
12 spaces for extended
custom label
NFS2-640 UL Listing Document — P/N 52741LD:H9 5/19/2022
N
lights supervisory LED
Y
lights fire alarm LED and activates CBE
N
lights supervisory LED
Y
lights supervisory LED
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED and activates CBE
Y
lights supervisory LED and activates CBE
N
lights pre-alarm LED and actives CBE
N
activates CBE
N
activates CBE
Y
activates CBE
(see note
below)
Y
activates CBE
(see note
below)
Table 7 Intelligent Detector Type Codes (3 of 3)
Blinking Type Code selection
P R O G R A M M O N I T O R
H A L L W A Y
0 9 _ _ _ _ _ _ _ _
Default zone
Laser smoke detector used to report supervisory
condition rather than alarm. Tracking.
Duct Laser smoke detector
Laser smoke detector used as a duct detector to
report supervisory condition rather than alarm.
Tracking.
Laser smoke detector used as a duct detector to
report supervisory condition rather than alarm.
Latching.
Assign to one or more FSL-751 detectors used to
monitor the quality of air entering the protected area.
The air quality measurement allows the VIEW
system to compensate for vehicle fumes, fog, or other
particles brought into the protected area through the
ventilation system. Poor air quality will lower the
sensitivity of all FSL-751 detectors on the SLC. The
detector sensitivity, however, remains within approved
limits (always less than 1% obscuration per foot).
190
190
warning.
135
o
15
Combination Photoelectric/heat detector without
freeze warning (Acclimate Plus)
Combination Photoelectric/heat detector with freeze
warning (Acclimate Plus, or IntelliQuad FSC-851
Photoelectric Multi-Criteria Smoke Sensor)
Multi-sensor smoke detector
Aspiration smoke detector
Aspiration detector supervision
Aspiration detector pre-alarm
Aspiration detector non-alarm
Used as a reference for other aspiration detectors on
the loop.
Combination Photoelectric/Heat detector. Photo
element activation generates a supervisory condition
Combination Photoelectric/Heat detector with low
temperature warning. Photo element activation
generates a supervisory condition.
20-character user-editable custom label.
W E S T E R N E N T R A N C E A N D
CBE list
(five zones)
o
F intelligent thermal sensor
o
F intelligent thermal sensor with low temperature
o
F intelligent thermal sensor
F per minute rate-of-rise detector
2 M 1 0 1
SLC address (001-159)
M (module)
SLC number (1 or 2)
®
29