P R O G R A M C O N T R O L
12 spaces for extended
custom label
Type Code
Silenceable (Y/N) Configuration
CONTROL
RELAY
BELL CIRCUIT
STROBE CKT
HORN CIRCUIT
AUDIBLE CKT
SPEAKER
ISOLATED NAC
ISOLATED SPK
REL END BELL
blank
1
REL CKT ULC
1
RELEASE CKT
1
RELEA.FORM C
REL AUDIBLE
NONRESET CTL
TELEPHONE
1
INSTANT RELE
ALARMS PEND
CONTROL NAC
GEN ALARM
GEN SUPERVIS
GEN TROUBLE
GENERAL PEND
TROUBLE PEND
MNS GENERAL
MNS CONTROL
MNS STROBE
MNS SPEAKER
MNS RELAY
1 The FCM-1-REL checks for shorts with all releasing type codes.
NFS2-640 UL Listing Document — P/N 52741LD:H9 5/19/2022
Blinking Type Code selection
0 0 _ _ _ _ _ _ _ _ I O W
Default zone
Switch Inhibit: I=selected; *=off (default)
Y
NAC
Y
Form-C relay
Y
NAC
Y
NAC
Y
NAC
Y
NAC
Y
NAC
Y
NAC
Y
NAC
N
NAC
Y
NAC
N
NAC
N
NAC
N
Form-C Relay
Y
NAC
N
Form-C Relay and NAC
N
NAC
N
NAC
N
NAC
Y
NAC
N
NAC
N
NAC
N
NAC
N
NAC
N
NAC
N
NAC
N
NAC
N
NAC
N
NAC
N
Relay
Table 9 Control Module Type Codes
20-character user-editable custom label
M O D U L E C O N T R O L 2 M 1 0 1
CBE list
(five zones)
Walk Test Selection: *=off
(default); W=selected
Silenceable: O =selected; *=off (default)
Device Function
Supervised NAC for notification appliance
Relay output
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC for notification appliance, used with audio isolators. Activates even
if there is a short on its NAC circuit. For ULC installations only.
Supervised NAC for speaker circuits, used with audio isolators. Activates even if
there is a short on its audio circuit. For ULC installations only.
Supervised NAC for notification appliance
Supervised NAC (for use when no other Type Code applies)
Releasing Circuit, power-limited (Class 2), supervised for opens, shorts and ground
faults (always non-silenceable)
Releasing circuit, non-power-limited, supervised for opens and ground faults
Relay output, contacts operate upon release
NAC, activated upon release
Relay output, unaffected by "System Reset" command
Standard Telephone circuit
NAC, short = normal; supervised for open circuits and ground faults. Always non-
silenceable and switch-inhibited.
Output that will activate upon receipt of an alarm condition, and remain in the alarm
state until all alarms have been acknowledged. It is programmed as "switch inhibit".
Supervised NAC
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) configured as a
Municipal Box Transmitter for NFPA 72 Auxiliary Fire Alarm Systems applications.
This Type ID can also be used for general alarm activation. It is programmed as
"switch inhibit".
Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated under any
Supervisory condition (includes sprinkler type). It is programmed as "switch inhibit".
Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated under any
System Trouble condition. It is programmed as "switch inhibit".
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will activate upon
receipt of an alarm and/or trouble condition, and remain in the ON state until all
events have been ACKNOWLEDGED.
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will activate upon
receipt of a trouble condition, and remain in the ON state until all troubles have been
ACKNOWLEDGED. It is programmed as "switch inhibit".
Mass notification supervised output.
Mass notification supervised NAC.
Mass notification supervised NAC.
Mass notification supervised NAC for speaker circuits.
Mass notification relay output.
2 M 1 0 1
SLC address (001-159)
M (module)
SLC number (1 or 2)
31