Seneca R-KEY-LT User Manual page 21

1-port modbus rtu/ascii gateway
Hide thumbs Also See for R-KEY-LT:
Table of Contents

Advertisement

SERVER #n MODE
Enable or not the selected server
SERVER #n TCP/IP PORT
Server#n TCP-IP port for the Modbus TCP-IP protocol
SERVER #n TCP/IP ADDRESS
Server#n IP address
SERVER TIMEOUT
Used to Set the server timeout before making a new TCP-IP call
SERVER #n START SLAVE ADDRESS
Used to Set the First Modbus station address slave connected to the Server #n.
SERVER #n LAST SLAVE ADDRESS
Used to Set the Last Modbus station address slave connected to the Serve r#n.
For example:
SERVER#1 START SLAVE ADDRESS = 1
SERVER#1 LAST SLAVE ADDRESS = 2
SERVER#2 START SLAVE ADDRESS = 3
SERVER#2 LAST SLAVE ADDRESS = 9
SERVER#3 START SLAVE ADDRESS = 10
SERVER#3 LAST SLAVE ADDRESS = 10
If the serial master makes a request to the slave address 1 the R-KEY-LT will request the registers from the
Modbus TCP-IP server #1.
If the serial master makes a request to the slave address 2 the R-KEY-LT will request the registers from the
Modbus TCP-IP server #2.
If the serial master makes a request to the slave address 3 the R-KEY-LT will request the registers from the
Modbus TCP-IP server #2.
...
If the serial master makes a request to the slave address 9 the R-KEY-LT will request the registers from the
Modbus TCP-IP server #2.