Technical data

6.2 Output

Figure 6-1
6.2
Output
Output
Rated voltage U
DC
out rated
Total tolerance, static ±
Static line regulation, approx.
Static load regulation, approx.
Residual ripple in the load range
Peak-peak, max.
Spikes peak-peak, max. (bandwidth, approx. 20 MHz)
Adjustment range
Output voltage can be adjusted
Output voltage setting
Remark
Operating display
Signaling
Switch-on/switch-off response
Starting delay, max.
Voltage rise, typ.
Rise time of the output voltage, max.
Rated current I
out rated
Current range
Active power output, typ.
28
Power failure buffering
6EP4436-0SB00-0AY0 (24 V/20 A)
Regulated, isolated DC voltage
24 V
2 %
0.1 %
0.2%
50 mV
200 mV
24 - 28.8 V
Yes
Via potentiometer
Max. 480 W
LED green for "24 V O.K."
Relay contact (NO contact, contact rating (isolated)
30 V AC / 0.5 A, 60 V DC / 0.3 A, 30 V DC / 1 A) for "24 V
O.K."
No overshoot of U
(soft start)
out
2.5 s
150 ms
500 ms
20 A
0 - 20 A
480 W