Burner Type; Gas Connection - Unigas E115X Manual Of Installation - Use - Maintenance

Gas - light oil burners
Table of Contents

Advertisement

Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Type
E115X
(1)
1

BURNER TYPE

2
FUEL
3
OPERATION (Available versions)
4
BLAST TUBE
5
DESTINATION COUNTRY
6
BURNER VERSION
7
EQUIPMENT
8

GAS CONNECTION

Technical Specifications
BURNER TYPE
Output
Fuel
Category
Gas rate- Natural gas
Gas pressure
Light oil rate
Oil viscosity
Oil density
Light oil train inlet pressure
Power supply
Total power consumption
Electric motor
Pump motor
Protection
Operation
Gas train 40 Connection
Gas train 50 Connection
Gas train 65
Gas train 80
Operating temperature
Storage Temperature
Working service
Note1:
All gas flow rates are referred to Stm
(net calorific value H
Note2:
Maximum gas pressure= 360 mbar (with Dungs MBDLE)
Maximum gas pressure= 500 mbar (with Siemens VGD or Dungs MultiBloc MBE)
Minimum gas pressure= see gas curves.
Warning:
Burners are suitable only for indoor operation with a maximum relative humidity of 80%
PART I: SPECIFICATIONS
Model
MG.
PR. S.
(2)
(3)
(4)
min. - max. kW
min.- max. (Stm
mbar
min. - max. kg/h
cSt @ 40°C
kg/m3
bar max
kW
kW
kW
Ø Valves / Connections
Ø Valves / Connections
Ø Valves / Connections
Ø Valves / Connections
°C
°C
3
/ h (1.013 mbar absolute pressure, 15° C temperature) and are valid for G20 gas
3
= 34,02 MJ / Stm
= 9,45 kWh / Stm
i
*.
A.
1.
40.
(5)
(6)
(7)
(8)
E115X - E150X - E180X
MG - Natural gas-Light oil
PR - Progressive
MD - Fully modulating
S - Standard,
SR = Standard blast tube + ABS polymer (silenced) air intake
LR = Extended blast tube + ABS polymer (silenced) air intake
* - see data plate
A - Standard
Y - SpecialeSpecial
1 = 2 gas valves + gas proving system
8 = 2 gas valves + gas proving system + maximum gas pressure switch
40 = Rp1
50 = Rp2
1/2
E115X MG..
300 - 1150
3
32 - 122
/h)
25 - 97
2
840
2
3,25
2,2
0,55
PR - Progressive MD - Fully modulating
40 / Rp 1
50 / Rp 2
65 / DN65
80 / DN80
-10 ÷ +50
-20 ÷ +60
3
);
6
65 = DN65
100 = DN100
E150X MG..
250 - 1550
MG - Natural gas-Light oil
(see next paragraph)
26 - 164
(see Note 2)
21 - 131
2
840
2
230V 3~ / 400V 3N ~ 50Hz
3,25
2,2
0,55
IP40
40 / Rp 1
1/2
1/2
50 / Rp 2
65 / DN65
80 / DN80
-10 ÷ +50
-20 ÷ +60
Intermitent
E180X MG..
320 - 1800
34 - 190
27 - 152
2
840
2
4,05
3
0,55
40 / Rp 1
1/2
50 / Rp 2
65 / DN65
80 / DN80
-10 ÷ +50
-20 ÷ +60