User Interface; First Start-Up - Unigas E115X Manual Of Installation - Use - Maintenance

Gas - light oil burners
Table of Contents

Advertisement

User interface :

+
First startup when PME is supplied or PME replacement:
First startup:
1) insert a new PME
2) turn the power on; The diplay shows "rst" and "PrC" one after the other.
3) keep pushing the INFO
4) at the end, "End" and "rst" appears one after the other; Later (2'), the control box locks out "Loc 138"
5) reset the control box by pressing the INFO
Now the display shows "OFF"; the burner is ready to be started.
Replacement:
1) Turn off the burner, replace the existing PME with a new one
2) For the first startup, repeat the above procedure, from step 2.
Button A
- Display preset output
- In lockout position: Power value to the time of fault
Info and Enter button
- Reset in the event of fault, changeover visual diagnostic of the cause of fault
(refer to chapter Diagnostics of cause of fault )
- button
- Display flame signal current 2 or phases display
- In lockout position: MMI phase to the time of fault
+ button
- Display flame signal current 1 or phases display
- In lockout position: MMI phase to the time of fault
3 multicolor signal lamp
- Refer to chapter "Blink code table"
+ and - button: Escape function
(press + and - simultaneously)
- No adoption of value
- One menu level up
- Keep depressed for >1second for backup / restore function
button more than 3 seconds; "run" appears; PME parameters will be transferred to LME
button (for less than 3 seconds)
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

E150xE180x

Table of Contents