Table of Contents

Advertisement

4.10 Status Messages

The following messages are displayed to show system
status. Notices are displayed in the Event History in
SiteTech when active but do not appear on the controller
display. Some status messages are displayed when a
Status Message
Always Off *
Always On *
Auto Locked *
(Chicago Code Active)
Common Fault
Common Warng
Default Pars Warning
(Default Parameters)
Emerg Pwr On
(Emergency Power System
Supplying Load)
Eng Cooldown
Fuel Spill *
* Programmable Interface Module (PIM) required.
[ Load management device required (LCM, load shed kit, or RXT with combined interface/ load management board).
TP-6881 7/15
Action
Description/ Comments
Notice
OnCuer Plus has been used to control
this PIM digital output. The digital output
is no longer controlled by the generator
set.
Notice
Applies to digital outputs B3 through B6
on the PIM only.
Notice
The digital output for Chicago Code
Active (PIM) is active (contacts closed),
indicating the digital input for Chicago
Code Active (PIM) is active (low) and
thus master switch is locked in the AUTO
position.
Notice
The digital output for Common Fault
(PIM) is active (contacts closed),
indicating the generator is shutdown for
any (all) fault.
Notice
The digital output for Common Warning
(PIM) is active (contacts closed),
indicating that any (all) warning is active.
Warning
The controller has been loaded with
default parameters.
Notice
The digital output for EPS Supplying
Load (PIM) is active (contacts closed),
indicating there is current output (>5%)
from the alternator, only if CTs are
installed.
Notice
The digital output for Engine Cooldown
Active (PIM) is active (contacts closed),
indicating the generator is running in
cooldown. (Delay 5 min.)
Notice
The digital output for Fuel Spill (PIM) is
active (contacts closed), indicating any of
the digital inputs for Fuel Tank Leak
Warning, Fuel Tank Leak Shutdown,
Engine Fuel Level Warning or Engine
Fuel Level Critically High (PIM) is active
(low).
digital input is activated; the optional Programmable
Interface Module (PIM) is required for display of those
messages as noted in the table.
Check
Click on the PIM output in
OnCue Plus to turn the output
on or off. See the OnCue
Plus Operation Manual.
To reset the PIM digital output
to a function controlled by the
generator set, use SiteTech
software to re-assign the
output event.
Check customer equipment
connected to the PIM module.
Check for faults and
troubleshoot any/all fault
conditions individually.
Check for warnings and
troubleshoot any/all warning
conditions individually.
Configure settings as required
for desired operation.
Nothing to check.
Check remote start circuit if it
was expected that the
generator should be running.
Consult ATS operations
manual.
Check customer equipment
connected to the PIM module.
Section 4 Troubleshooting