Air Cleaner, 10/12Resv/Resvl Models - Kohler Power Systems 8RESV Service Manual

Residential/commercial generator sets
Hide thumbs Also See for Power Systems 8RESV:
Table of Contents

Advertisement

2.4.2
Air Cleaner, 10/12RESV/RESVL
Models
The engine is equipped with a replaceable, high density
paper air cleaner element. See Figure 2-7.
5
4
1. Air cleaner cover lever
2. Air cleaner element
3. Base
Figure 2-7 Air Cleaner Components
Check the air cleaner daily or before starting the engine.
Check for a buildup of dirt and debris around the air
cleaner system. Keep this area clean. Also check for
loose or damaged components. Replace all bent or
damaged air cleaner components.
Note: Operating the engine with loose or damaged air
cleaner components could allow unfiltered air
into the engine causing premature wear and
failure.
22
Section 2 Scheduled Maintenance
1
2
3
tp6515
4. Blower housing
5. Air cleaner cover
Paper Element Service
Replace the paper element at the intervals indicated in
the service schedule. See Figure 2-7 for the air cleaner
components.
1. Press the OFF button on the generator set
controller.
2. Disconnect the utility power to the generator set.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Rotate the air cleaner cover levers outward to
unlock cover; remove the air cleaner cover.
5. Remove the paper element from the base.
6. Do not wash the paper element or use pressurized
air, as this will damage the element. Replace a
dirty, bent, or damaged element. Handle new
elements carefully; do not use if the sealing
surfaces are bent or damaged.
7. When servicing the air cleaner, check the air
cleaner base. Make sure it is secured and not bent
or damaged. Also, check the element cover for
damage or improper fit. Replace all damaged air
cleaner components.
Note: If any loose dirt or debris fell on the air cleaner
base when the element was removed, carefully
remove it and wipe the base clean. Be careful
that none of it drops into the intake throat.
8. Reinstall the paper element onto the air cleaner
base. Make sure the element is flat and properly
seated.
9. Position the air cleaner cover with levers outward
over air cleaner; turn levers inward to lock.
10. When element replacement is necessary, order
genuine Kohler parts.
11. Reconnect the power to the battery charger.
12. Reconnect the generator set engine starting
battery, negative (--) lead last.
TP-6881 7/15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents