YASKAWA VS-616 Series Option Instruction Manual page 12

Isolated analog monitor card
Table of Contents

Advertisement

Terminal
TB1-1
Channel 1
TB1-2
Channel 2
Note: Refer to "OUTPUT SIGNAL LEVEL SETTING" for 100% output signal level in output content.
Page 12
Table 8: Programming Settings With VS-616H3
Program
Constant No.
bn-15
bn-17
VS-616/676 Series Option Instruction Manual: Isolated Analog Monitor Card AO-12B2
Set
Output Contents
Value
Frequency reference:
1
Max. frequency/100%
Output frequency:
2
Max. frequency/100%
Output current
3
Rated current/100%
Output voltage reference:
4
input voltage/100%
DC voltage (V
5
400v/100% (200V class)
Output Power
6
(+ indication):
Rated power (kW) 100%
Speed feedback (PG,G):
17
Max. frequency/100%
Compensated
18
frequency (PG,TG):
Max. frequency/100%
Voltage feedback (AVR):
19
Input voltage/100%
Compensated voltage (AVR):
20
Input voltage/100%
Momentary reduced value:
21
Max. frequency/100%
Output
Accuracy
1.0%
3.0%
1.5%
1.5%
)
PN
10%