Illustration Of Dimensions; Dimensions; Dimensions Data Notes - Coleman LX Series Technical Manual

4.3 seer2 split-system air conditioner - single-phase
Hide thumbs Also See for LX Series:
Table of Contents

Advertisement

6.
For applications with non-standard vapor line sizes, refer to the Applications and accessories
section.
7.
The unit charge is correct for the outdoor unit, smallest matched indoor unit, and 15 ft
of refrigerant tubing. For tubing lengths other than 15 ft, add or subtract the amount of
refrigerant, using the difference in actual refrigeration piping length (not the equivalent
length) multiplied by the per foot value.
‡ The adapter fitting must be field installed for the required 1 1/8 in. refrigeration piping.

Illustration of dimensions

Figure 2: Unit dimensions

Dimensions

Table 3: Dimensions
Outdoor unit
Dimensions (in.)
model
A
TCE2B18S21S
30
TCE2B24S21S
30
TCE2B30S21S
36 1/4
TCE2B36S21S
33 1/4
TCE2B42S21S
36 1/4
TCE2B48S21S
33 1/4
TCE2B60S21S
36 1/4

Dimensions data notes

• ‡ The adapter fitting must be field installed for the required 1 1/8 in. refrigeration piping.
• All dimensions are in inches and are subject to change without notice.
• The overall height is from the bottom of the base pan to the top of the fan guard.
• The overall length and width include screw heads.
Coleman Technical Guide: LX Series TCE2B Models - 14.3 SEER2 Split-System Air Conditioner - Single-Phase
B
C
29 1/4
29 1/4
29 1/4
29 1/4
29 1/4
29 1/4
35 1/4
31 3/4
35 1/4
31 3/4
35 1/4
31 3/4
38
34 1/4
Johnson Controls Ducted Systems
Refrigerant connection service valve
size
Liquid
Vapor
3/4
3/8
7/8
7/8‡
11