Cooling Performance Data - 1.5 Ton; Cooling Performance Data Notes; Multipliers For Determining The Performance With Other Indoor Sections; Cool Multiplier Airhandler - 1.5 Ton - Coleman LX Series Technical Manual

4.3 seer2 split-system air conditioner - single-phase
Hide thumbs Also See for LX Series:
Table of Contents

Advertisement

Cooling performance data - 1.5 ton

Table 18: Cooling performance data - TCE2B18S21S with indoor coil XAFA24BXXN1
Air
ID CFM
450
temperature
ID DB
80
entering
(°F)
outdoor unit
ID WB
57
(°F)
(°F)
55
T.C.
16.8
S.C.
16.8
kW
0.92
T.C.
65
16.8
S.C.
16.8
kW
1.10
75
T.C.
16.2
S.C.
16.2
kW
1.17
85
T.C.
15.6
S.C.
15.6
kW
1.25
95
T.C.
15.0
S.C.
15.0
kW
1.39
105
T.C.
14.4
S.C.
14.4
kW
1.62
T.C.
115
13.8
S.C.
13.8
kW
1.82
125
T.C.
12.2
S.C.
12.2
kW
2.10

Cooling performance data notes

• All capacities include indoor fan heat. kW values are for the system (outdoor + indoor).
• Green shaded cells are ACCA (TVA) conditions.
• Blue shaded cells are AHRI conditions.
Multipliers for determining the performance with other
indoor sections
Note: For dry bulb temperatures different than those listed (between 73°F to 87°F), sensible
capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and
decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

Cool multiplier airhandler - 1.5 ton

Table 19: Cool multiplier air handler - 1.5 ton
Air handler model
Indoor coil model
CF/CM/CU30B
CF/CM30A
CF/CM30C
XAF/XAUB30C
Coleman Technical Guide: LX Series TCE2B Models - 14.3 SEER2 Split-System Air Conditioner - Single-Phase
600
80
75
80
80
80
62
62
67
72
57
18.9
18.8
20.5
22.9
18.3
15.8
13.5
13.1
11.4
18.3
0.93
0.93
0.91
0.87
0.95
18.3
18.2
20.0
22.0
18.3
15.4
13.2
13.2
11.0
18.3
1.07
1.08
1.05
1.01
1.14
17.5
17.4
19.2
21.1
17.6
14.9
12.7
12.8
10.5
17.6
1.15
1.16
1.13
1.11
1.22
16.7
16.7
18.3
20.2
16.9
14.5
12.3
12.3
10.1
16.9
1.24
1.24
1.22
1.20
1.30
16.0
15.9
17.5
19.3
16.2
14.0
11.9
12.0
9.8
16.2
1.39
1.39
1.38
1.36
1.45
15.1
15.1
16.6
18.2
15.5
13.7
11.6
11.6
9.4
15.5
1.62
1.62
1.62
1.61
1.69
14.2
14.2
15.7
17.3
14.8
13.3
11.2
11.3
9.1
14.8
1.82
1.82
1.81
1.80
1.88
12.6
12.7
14.4
16.4
13.4
12.5
10.3
10.6
8.8
13.4
2.09
2.09
2.06
2.02
2.12
Total capacity
1.00
1.00
1.00
1.00
Johnson Controls Ducted Systems
750
80
75
80
80
80
62
62
67
72
57
19.8
19.7
21.9
23.9
19.3
18.1
15.2
15.2
12.3
19.3
0.98
0.98
0.94
0.91
0.99
19.1
19.1
21.0
22.9
19.4
17.4
14.7
14.7
11.9
19.4
1.12
1.13
1.09
1.05
1.18
18.2
18.2
20.0
21.9
18.5
16.9
14.2
14.2
11.4
18.5
1.21
1.21
1.19
1.16
1.27
17.3
17.4
19.1
20.9
17.8
16.3
13.7
13.8
11.0
17.8
1.30
1.30
1.28
1.26
1.36
16.5
16.5
18.2
19.9
17.0
15.8
13.3
13.3
10.6
17.0
1.45
1.45
1.43
1.42
1.51
15.5
15.6
17.1
18.7
16.2
15.5
12.9
13.0
10.2
16.2
1.69
1.69
1.68
1.67
1.75
14.8
14.7
16.2
17.8
15.4
14.8
12.6
12.6
9.9
15.4
1.88
1.88
1.88
1.87
1.94
13.8
13.3
15.1
17.0
14.4
13.8
12.1
12.3
9.7
14.4
2.12
2.13
2.11
2.09
2.16
Sensible capacity
0.96
0.96
0.96
1.02
80
75
80
80
62
62
67
72
20.3
20.3
22.7
24.5
20.1
16.7
17.1
13.0
1.02
1.03
0.99
0.96
19.6
19.6
21.5
23.4
19.1
15.9
16.0
12.7
1.18
1.18
1.14
1.11
18.6
18.7
20.5
22.4
18.5
15.4
15.5
12.2
1.27
1.27
1.24
1.21
17.8
17.8
19.5
21.3
17.8
14.9
14.9
11.7
1.36
1.36
1.34
1.32
17.0
16.9
18.6
20.3
17.0
14.4
14.5
11.3
1.51
1.51
1.50
1.48
16.2
15.8
17.4
19.0
16.2
14.0
14.1
10.9
1.75
1.75
1.74
1.74
15.4
14.8
16.4
18.0
15.4
13.7
13.8
10.6
1.94
1.95
1.94
1.93
14.8
13.8
15.5
17.4
14.8
13.7
13.9
10.5
2.16
2.17
2.17
2.17
kW
1.00
1.00
1.00
1.00
89

Hide quick links: