Performance Data - 2 Ton; Condenser Only Performance Data - 2 Ton; Condenser Only Performance Data Notes - Coleman LX Series Technical Manual

4.3 seer2 split-system air conditioner - single-phase
Hide thumbs Also See for LX Series:
Table of Contents

Advertisement

Performance data - 2 ton

See the following tables for performance and multiplier data for the TCE2B24S21S unit.

Condenser only performance data - 2 ton

Table 21: TCE2B24S21S condenser table
Saturated suction
at compressor
Temperature
Pressure
55 °F
(°F)
(psig)
MBH
35
107
23.8
0.93
40
118
26.2
0.90
45
130
28.8
0.87
50
142
31.6
0.83
55
156
34.4
0.79

Condenser only performance data notes

• For outdoor unit (condenser) performance only. Data does not include the effects of air
handler power or heat.
• Performance based on 15°F subcooling and 15°F superheat at the outdoor unit base valves:
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
• Maximum recommended condensing temperature is 140°F.
Coleman Technical Guide: LX Series TCE2B Models - 14.3 SEER2 Split-System Air Conditioner - Single-Phase
65 °F
75 °F
kW
MBH
kW
MBH
kW
22.6
1.09
21.3
1.25
24.8
1.07
23.4
1.23
27.3
1.04
25.8
1.21
29.9
1.01
28.3
1.19
32.6
0.98
30.9
1.17
Johnson Controls Ducted Systems
Outdoor ambient temperature
85 °F
95 °F
105 °F
MBH
kW
MBH
kW
MBH
20.0
1.42
18.7
1.61
17.3
22.1
1.41
20.6
1.59
19.1
24.3
1.39
22.7
1.58
21.1
26.6
1.37
24.9
1.57
23.2
29.1
1.35
27.3
1.55
25.4
115 °F
125 °F
kW
MBH
kW
MBH
kW
1.82
15.8
2.08
14.1
2.40
1.81
17.5
2.06
15.7
2.37
1.80
19.3
2.05
17.4
2.35
1.79
21.3
2.04
19.3
2.33
1.77
23.4
2.02
21.2
2.32
97