Performance data - 4 ton
See the following tables for performance and multiplier data for the TCE2B48S21S unit.
Condenser only performance data - 4 ton
Table 37: TCE2B48S21S Condenser Table
Saturated suction
at compressor
Temperature
Pressure
55 °F
(°F)
(psig)
MBH
35
107
48.3
1.99
40
118
53.1
1.99
45
130
58.2
1.97
50
142
63.7
1.95
55
156
69.5
1.92
Condenser only performance data notes
• For outdoor unit (condenser) performance only. Data does not include the effects of air
handler power or heat.
• Performance based on 15°F subcooling and 15°F superheat at the outdoor unit base valves:
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
• Maximum recommended condensing temperature is 140°F.
156
Coleman Technical Guide: LX Series TCE2B Models - 14.3 SEER2 Split-System Air Conditioner - Single-Phase
65 °F
75 °F
kW
MBH
kW
MBH
kW
46.1
2.33
43.6
2.65
50.6
2.33
47.8
2.66
55.4
2.32
52.4
2.66
60.6
2.31
57.2
2.66
66.1
2.29
62.4
2.64
Johnson Controls Ducted Systems
Outdoor ambient temperature
85 °F
95 °F
105 °F
MBH
kW
MBH
kW
MBH
40.8
2.97
37.9
3.31
34.9
44.9
2.99
41.7
3.34
38.5
49.2
3.00
45.8
3.36
42.3
53.7
3.01
50.1
3.37
46.4
58.6
3.00
54.7
3.38
50.7
115 °F
125 °F
kW
MBH
kW
MBH
kW
3.68
31.7
4.11
28.5
4.60
3.72
35.2
4.14
31.7
4.64
3.75
38.8
4.18
35.1
4.67
3.77
42.6
4.20
38.7
4.70
3.78
46.7
4.22
42.5
4.72