500-8067.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * Revision 03
NOTE!
When connecting cable plugs type Raychem RICS5xxx with surge arresters
type RDA 24, earth the cable as shown below.
The cable shield of the cables L1, L2, L3 is earthed via cable lugs/earthing bolts
size M10 at the upper cross member.
For details, please refer to the order documents.
For connection of unscreened cable plugs / surge arresters, keep the necessary
minimum distances according to the manufacturer's instructions.
If the minimum distances cannot be kept, please contact your regional Siemens
representative.
Installation
a
Cable (phase L1)
s
Cable (phase L2)
d
Cable (phase L3)
f
Upper cross member
89