Siemens 8DJH Series Installation And Operating Instructions Manual page 58

Medium-voltage switchgear
Table of Contents

Advertisement

Description
58
Transformer
U [kV]
S
[kVA]
u
N
K
15-17.5
630
4
800
5- 6
1000
5-6
1250
5-6
20-24
50
4
75
4
100
4
125
4
160
4
200
4
250
4
315
4
400
4
500
4
630
4
800
5-6
1000
5-6
1250
5-6
1600
5-6
2000
5-6
U
Rated system voltage
S
Rated power
N
U
Relative impedance voltage
K
I
Rated current
1
I
Rated current of fuse
S
U
Rated voltage of fuse
S
e
Reference dimension
NOTE!
- For switchgear with rated voltages up to 12 kV, a fuse slide for
HV HRC fuse-links with dimension 292 mm is normally provided.
- 7 .2 kV fuse-links with dimension 192 mm as well as 24 kV fuse-links with
dimension 292 mm are not permissible.
Revision 03 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * 500-8067.9
HV HRC fuse
[%]
I
[A]
I
[A] U
1
s
s
24.3
40
10-17.5
40
10-24
50
10-17.5
50
10-24
63
10-24
30.9
63
10-24
38.5
80
10-24
48.2
100
10-24
1.5
6.3
10-24
2.2
6.3
10-24
2.9
6.3
10-24
3.6
10
10-24
4.7
10
10-24
5.8
16
10-24
7.3
16
10-24
9.2
16
10-24
20
10-24
11.6
20
10-24
25
10-24
14.5
25
10-24
31.5
10-24
18.2
31.5
10-24
40
10-24
23.1
31.5
10-24
40
10-24
29
50
10-24
63
10-24
36
80
10-24
46.5
100
10-24
57.8
[kV]
e [mm]
Order no.
442
30 231 13.40
442
30 006 13.40
442
30 232 13.50
442
30 014 13.50
442
30 014 43.63
442
30 014 43.63
442
30 014 43.80
442
30 022 43.100
442
30 006 13.6,3
442
30 006 13.6,3
442
30 006 13.6,3
442
30 006 13.10
442
30 006 13.10
442
30 006 13.16
442
30 006 13.16
442
30 006 13.16
442
30 006 13.20
442
30 006 13.20
442
30 006 13.25
442
30 006 13.25
442
30 006 13.31,5
442
30 006 13.31,5
442
30 006 13.40
442
30 006 13.31,5
442
30 006 13.40
442
30 014 13.50
442
30 014 43.63
442
30 014 43.80
442
30 022 43.100
On request

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents