In the example shown, the I/O associations are:
A
Fault will immediately activate Sounder Circuit 1
B
Evacuation will immediately activate: Sounder Circuit 1, Output Modules 001 and 002
C
Output Module 001 will be activated by:
•
Evacuation command
•
One device in alarm from Zone 2 and one device in alarm from Zone 3
•
One device in alarm from Zone 5 once delay time is finished
D
Output Module 002 will be activated by:
•
Evacuation command
•
One device in alarm from Zone 1
•
Two devices in alarm from Zone 4
•
One device in alarm from Zone 5 once delay time is finished