Fire Alarm Control Panel LT-32 / LT-159
3

INSTALLATION OVERVIEW

The panel range is designed for mounting onto an internal wall of a protected building, and is not suitable for mounting on outdoor applications.
1. Install the panel enclosure in accordance with the instructions reported in this manual.
2. Bring the field wiring/cables through the recommended entry points on the backbox. Prepare all cable/wiring entry with appropriate fire industry-approved cable
glands and label all field wiring correctly to aid termination.
3. Install a fire industry-approved, AC mains power supply isolator 'fused spur unit' close to the FACP. The mains supply cable must be brought into the enclosure,
using a recommended cable entry point.
4. Use this manual for recommendations on how to install batteries inside the enclosure.
5. Once individual cables are checked, make the wiring of each circuit. The battery link is fitted during the commissioning power up stage.
10
M-168.1-SERIE-LT-EN / 08.2022