Single phase connection (32 A)
•
Single-phase connection (1 1N, 220 240 V~ /50 60 Hz):
-
Voltage between line and neutral conductor is 220 240 V~. Install
a jumper between terminals 1 and 2, and between terminals 4
and 5.
-
The circuit should be fitted with a fuse of at least 32 A. Power
cord core cross-sectional area should be at least 4 mm².
2-phase connection (16A)
•
2 phases, 1 neutral conductor (2 1N, 380 415 V~ /50 60 Hz):
-
Voltage between the line and neutral conductor is 220 240 V~.;
voltage between lines is 380 415 V~. Install a jumper between
the terminals 4 and 5. The circuit should be fitted with at least
two fuses of at least 16 A each. Power cord core cross-sectional
area should be at least 1.5 mm².
•
2 phases, 2 neutral conductors (2 2N, 220 240 V 2 2N ~ /50 60Hz):
-
Voltage between phases and neutral conductor is 220-240 V~.
-
The circuit should be fitted with at least two fuses of at least 16 A
each. Power cord core cross-sectional area should be at least
1.5 mm2.
Appliances with a width of 30 centimetres (two cooking zones) only allow
single-phase connection. The diameter of the power cord should be at
least 1.5 mm²!