Ferrule-Type Terminals
Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent
ferrule-type terminals with the specifications listed in
proper connections.
Note: Properly trim wire ends so loose wire ends do not extend from the crimp terminals.
Ferrule-Type
Terminal
6 mm
d2
d1
L
Terminal Functions
Terminal
V1
Analog voltage output 1
V2
Analog voltage output 2
AC
Common
FE
Ground
<1> Set the functions and output levels for terminals V1 and V2 using unit parameters. See the unit Instruction Manual
for directions on setting parameters.
YASKAWA ELECTRIC TOBP C730600 40E 1000-Series Option AO-A3 Installation Manual
Table 3 Ferrule-Type Terminal Sizes
Wire Gauge
Phoenix Contact
2
mm
0.25 (24 AWG)
AI 0.25 - 6YE
0.34 (22 AWG)
AI 0.34 - 6TQ
0.5 (20 AWG)
Table 4 Option Terminal Functions
Function
Signal Level
Model
mm (in)
10.5 (13/32)
10.5 (13/32)
AI 0.5 - 6WH
14 (9/16)
• Analog voltage output for an external monitoring
device
-10 to 10 V
Output resolution 11-bit plus sign (1/2048)
• Max. load current 3 mA
0 V
Common for analog voltage output
Used for grounding shielded lines
5 Installation Procedure
Table 5
for wiring to ensure
L
d1
mm (in)
0.8 (1/32)
0.8 (1/32)
1.1 (3/64)
Description
<1>
d2
mm (in)
2 (5/64)
2 (5/64)
2.5 (3/32)
19