YASKAWA 1000 Series Installation Manual page 17

Analog monitor
Hide thumbs Also See for 1000 Series:

Advertisement

4.
Prepare and connect the wire ends as shown in
Wire Gauges and Tightening Torques on page 18
tightening torque is applied to each terminal. Take particular precaution to ensure
that each wire is properly connected and wire insulation is not accidentally pinched
into electrical terminals.
WARNING! Fire Hazard. Tighten all terminal screws according to the specified tightening torque. Loose
electrical connections could result in death or serious injury by fire due to overheating electrical connections.
Tightening screws beyond the specified tightening torque may cause erroneous operation, damage the
terminal block, or cause a fire.
NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not
contact other wiring. Insufficient insulation may cause a short circuit and damage the option or unit.
Figure 6
Figure 7
Preparing wire ends:
Pull back the shielding and lightly
twist the end with fingers, keeping
the ends from fraying.
YASKAWA ELECTRIC TOBP C730600 40E 1000-Series Option AO-A3 Installation Manual
Option terminal
FE
Figure 6 Preparing Ends of Shielded Cable
about 5.5 mm (7/32")
When not using
crimped insulated
sleeves
Loosen the screws and
insert the wire into the
opening on the terminal block.
Figure 7 Preparing and Connecting Cable Wiring
Figure 6
Insulation
To customer
circuit
Shield sheath
(Insulate with electrical tape
or shrink tubing)
Screwdriver blade size
Blade depth of
0.4 mm or less
Blade width of
2.5 mm or less
To customer circuit
(do not solder ends)
5 Installation Procedure
and
Figure
7. Refer to
to confirm that the proper
AO
AO
Option terminal block
17