Ratings, Specifications and Features

Emissions

AC Line Conducted Emissions
Radiated RF Emissions

Immunity

Electrostatic Discharge
RF Radiated Fields
Electrical Fast Transients
Lightning Surge
Conducted RF Common Mode
Power Frequency Magnetic Field
Voltage Dips/Short Variations
Voltage Dips/Short Variations
*With appropriate installation
EN 55032:2015
EN 55032:2015
IEC61000-4-2: 2008
EN 61000-4-3: 2006
+A1:2008 +A2:2010
EN61000-4-4: 2004+A1:2010 Power line pulses of ± 1 kV;
IEC61000-4-5: 2005
EN61000-4-6: 2009
IEC61000-4-8:2009
IEC61000-4-11:2004
SEMI F47-0706
4
OPERATION MANUAL
(0.15-30 MHz) Class A with external filter *
0-1000 MHz Class A with external filter *
+/-8 kV Air
+/-4 kV Contact
3 V/m from 80-1000 MHz;
(80% AM at 1kHz)
I/O line pulses of ± 0.5 kV
±4kV common mode
±2kV differential mode
150 kHz - 80 MHz at 3 Vrms
1 kHz 80% amplitude modulated
30A/m (Continuous), 300A/m (Short)
Dip to 0% of nom. line for 0.5 cycles - Criteria C
Dip to 0% of nom. line for 1 cycles - Criteria C
Dip to 40% of nom. line for 0.2 seconds - Criteria C
Dip to 70% of nom. line for 0.5 seconds - Criteria C
Dip to 80% of nom. line for 5 seconds - Criteria C
Dip to 50% of nom. line for 10 cycles - Criteria C
Dip to 70% of nom. line for 25 cycles - Criteria C
Dip to 80% of nom. line for 50 cycles - Criteria C
TPF45000-385
POWER SUPPLY
Table 1
3 February 2022

Advertisement

Table of Contents
loading