4. Recovering to Factory Setting and Updating Version

In the chapter, we will explain the functions setting by hardware Rotary Switch, including
"Recovering to Factory Setting" and "Updating Version" that supported since Version 1.0.0.3.

4.1. Recovering to Factory Setting (Rotary Switch: 8)

Turn the Rotary Switch of UA-5200 series to "8" can recover to the factory setting. The steps:
1.
Power off the UA-5200 hardware, and turn the Rotary Switch to "8".
2.
Reboot the UA-5200 and wait a long buzzer sound that means of doing the recovering.
3.
Wait until two long buzzer sounds, and then turn the Rotary Switch to "0".
Reboot the UA-5200 again, and the system will recover to the factory settings.

4.2. Updating the Version via USB (Rotary Switch: 9)

Turn the Rotary Switch of UA-5200 series to "9" can update the Middleware version via USB.
1.
Power off the UA-5200 hardware, and turn the Rotary Switch to "9".
2.
Download the Middleware package file of the UA-5200 hardware corresponding model.
The download website:
3.
Save the Middleware package file into an empty USB drive and put to the UA-5200 USB port.
4.
Reboot the UA-5200 and wait a long buzzer sound that means of doing the version updating.
5.
Wait until two long buzzer sounds, and then turn the Rotary Switch to "0".
6.
Reboot the UA-5200 again, and the system will update to the version of the package file.
ftp.icpdas.com.tw/pub/cd/UA-5000/middleware