MILLIVOLT VALVES
Natural gas will have a manifold pressure of approximately 3.5" w.c.
for maximum input or 1.7" w.c. for minimum input at the pressure
regulator outlet with the inlet pressure to the pressure regulator
from a minimum of 4.5" w.c. for the purpose of input adjustment to
a maximum of 10.5" w.c.
Propane gas will have a manifold pressure approximately 10.0"w.c.
pressure regulator outlet with the inlet pressure to the pressure
regulator from a minimum of 11.0"w.c. for the purpose of input
adjustment to a maximum of 13.0"w.c.
HYDRAULIC THERMOSTAT VALVES
Natural gas will have a manifold pressure of approximately 6.0"
w.c. at the pressure regulator outlet with the inlet pressure to the
pressure regulator from a minimum of 7.0" w.c. for the purpose of
input adjustment to a maximum of 10.5" w.c.
No greeting cards, stockings or ornamentation of any type
heat can ignite combustibles.
Page 16

CLEARANCES

MINIMUM CLEARANCE
TO PERPENDICULAR
COMBUSTIBLE SIDE- W ALL
Figure 10
Propane gas will have a manifold pressure approximately 10.0"w.c.
at the pressure regulator outlet with the inlet pressure to the pressure
regulator from a minimum of 11.0"w.c. for the purpose of input
adjustment to a maximum of 13.0"w.c.
A test gage connection is located downstream of the gas appliance
pressure regulator for measuring gas pressure. The connection is
a 1/8 inch N.P.T. plugged tapping.
Millivolt Control Valve
The valve regulator controls the burner pressure which should be
checked at the pressure test point. Turn captured screw counter
clockwise 2 or 3 turns and then place tubing to pressure gauge over
to re-seal. Do not over torque. Check for gas leaks.