Atlantic Loria 6000 R32 Installation Manual

Atlantic Loria 6000 R32 Installation Manual

Air/water heat pump single service split system
Hide thumbs Also See for Loria 6000 R32:

Advertisement

Quick Links

INSTALLATION
Loria 6000 R32
Air/water heat pump single service split system
Outdoor unit
WOYA060KLT
WOYA080KLT
WOYA100KLT
Hydraulic unit
023015
023016
024158
U0710280_2256_EN_1
20/09/2021
EN
For professionals
To be kept by the user for future reference

Advertisement

Table of Contents
loading

Summary of Contents for Atlantic Loria 6000 R32

  • Page 1 INSTALLATION Loria 6000 R32 Air/water heat pump single service split system Outdoor unit WOYA060KLT WOYA080KLT WOYA100KLT Hydraulic unit 023015 023016 024158 U0710280_2256_EN_1 For professionals 20/09/2021 To be kept by the user for future reference...
  • Page 2 ■ Installation and maintenance rules ■ Containment of refrigeration circuits The appliance must be installed and maintained All refrigeration circuits are sensitive to dust and by an approved professional in accordance with moisture contamination. If any such pollutants the prevailing regulations and code of practice, in penetrate the refrigeration circuit, they can aff...
  • Page 3 ■ Characteristics of the electrical power supply • Connecting to screw terminals Use of ring terminals or tips is prohibited. Always check that the electric power supply is switched off before works. - Always choose a rigid wire that complies with current standards.
  • Page 4: Table Of Contents

    Setting parameters ..... . . 50 Displaying information ..... 56 - 4 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 5 Important information that must always be kept in Warning : Slightly fl ammable refrigerant. mind. Tips and advice Read the installation manual Bad practice Read the operating manual Read the installation and operating manuals Loria 6000 R32 / INSTALLATION / 2256 - EN - 5 -...
  • Page 6: Description Of The Equipment

    • Condensate drain pan (Models 4/6/8 - ref. 074 008). for connecting a DHW tank • Container bottom tracer (ref. 809 644). (with built-in electrical back-ups). • Outdoor temperature sensor (ref. 074 203). - 6 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 7: Specifi Cations

    The acoustic power is a measurement made in the laboratory of the power of the noise emitted but contrary to the noise level, it does not correspond to the measurement of what is felt. Loria 6000 R32 / INSTALLATION / 2256 - EN - 7 -...
  • Page 8 ■ Outdoor Unit, models 4, 6 ■ Outdoor Unit, model 8 ■ Outdoor Unit, model 10 fi g. 1 - Dimensions in mm - 8 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 9 Front view Ø 1/4” Ø 1/2” Ø 26x34 1” Ø 26x34 1” Dimensions of the hydraulic unit, see § page 18 fi g. 2 - Dimensions in mm Loria 6000 R32 / INSTALLATION / 2256 - EN - 9 -...
  • Page 10 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 Temperature °C fi g. 5 - Ohmic value of the sensors (outdoor unit) - 10 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 11: Description

    fi ns and grooved 4-way valve. copper tubes. Anti-corrosion treated bodywork. 13. Pressure Switch. Main circuit electronic expansion valve. 14. Pressure sensor. fi g. 6 - Components Loria 6000 R32 / INSTALLATION / 2256 - EN - 11 -...
  • Page 12 PAC -Heat pump Ev - Evaporator Cp - Compressor Cn - Condenser Dt - Expansion valve fi g. 7 - Operating principle of a heat pump - 12 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 13: Operating Principle

    - Legionella cycle for domestic hot water. - Minimum fl ow detection. - Frost protection. - Electrical back-up safety thermostat. When the heat pump is equipped with options and associated kits. Loria 6000 R32 / INSTALLATION / 2256 - EN - 13 -...
  • Page 14: Layout

    fi g. 11 - Open the outdoor unit model 10 Poignées handles fi g. 9 - Recommended example of refrigerant connections layout fi g. 12 - Transport of the outdoor unit model 10 - 14 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 15: Installing The Outdoor Unit

    L = 200 mm max 500 mm M = 300 mm max fi g. 13 - Minimum installation clearances around the outdoor unit (model 4, 6 & 8 ) Loria 6000 R32 / INSTALLATION / 2256 - EN - 15 -...
  • Page 16 M = 300 mm max 500 mm N = 500 mm max 600 mm fi g. 14 - Minimum installation clearances around the outdoor unit (model 10 ) - 16 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 17 Trace heating must heat not only the drain pipe but also the bottom of the appliance's condensate collection tank. fi g. 15 - Positioning the outdoor unit, discharging condensates Loria 6000 R32 / INSTALLATION / 2256 - EN - 17 -...
  • Page 18: Installation Of The Hydraulic Unit

    fi nal connection, take care to put the caps back in position to avoid any pollution of the refrigeration circuit (sealing with adhesive is prohibited). fi g. 17 - Removing the front panel - 18 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 20 R32 gas 1220 1270 1730 charge 25 m min room volume R32 gas 1345 1395 1830 charge 30 m min room volume fi g. 18 - Minimum room volume - 20 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 21 1100 600 No requirement 1170 600 1300 700 1400 750 1500 800 1600 850 1700 900 1800 950 1840 950 fi g. 19 - Section of the opening Loria 6000 R32 / INSTALLATION / 2256 - EN - 21 -...
  • Page 22 Minimal section (Smin) of the low opening (cm 1000 No requirement 1100 1170 1300 1400 1500 1600 1700 1800 1840 fi g. 23 - Minimal section of the opening - 22 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 23 See fi g. 23 and fi g. 21 Voir figure xx pxx Ajout d’un détecteur Add a detector and a mechanical ventilation d’une ventilation mécanique fi g. 24 - Min. room surface Loria 6000 R32 / INSTALLATION / 2256 - EN - 23 -...
  • Page 24 - Hook the appliance onto its support. 206 mm Weight of hydraulic unit (full of water): 46 kg mini mini 6 mm fi g. 25 - Mounting bracket - 24 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 26: Refrigeration Connections

    fl aring tool's tube. - After fl aring, check the state of the working radius (L). This must not present any scratches or signs of fracturing. Also check the dimension (B). - 26 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 27 Plug (A) and (B) : see fi g. 58, page 67. 15.88 (5/8") 2.9 to 3.1 19.7 fi g. 27 - Tightening torques fi g. 26 - Flaring of the fl are connections Loria 6000 R32 / INSTALLATION / 2256 - EN - 27 -...
  • Page 28 R1 adapter depending on model "Gas" valve Outdoor unit Flare nut Flare nut "Gas" refrigerating connection diameter D1 fi g. 28 - Refrigerating link connection (accepted diameters and lengths) - 28 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 29: Checks And Connection

    Azote Nitrogen L i q u i d Liaison connection liquide Azote Nitrogen fi g. 29 - Checking refrigeration connections fi g. 30 - Additional fi lling label Loria 6000 R32 / INSTALLATION / 2256 - EN - 29 -...
  • Page 30 (set of pressure gauges). Always fi ll in the liquid phase. Never exceed the maximum length or diff erence in level. Liquid fi g. 31 - Gas bottle R32 - 30 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 31: Collecting Refrigerant In The Outdoor Unit

    "gas" and "liquid" valves. After 2 to 3 minutes repeat fi g. 32 - Location of DIP switches and LEDs on the the pump down operation. hydraulic unit interface board Loria 6000 R32 / INSTALLATION / 2256 - EN - 31 -...
  • Page 32: Hydraulic Connections

    (ref. V-M). page In the event of non-compliance with the minimum fl ow rate, the HP shuts down (error 131 - see "Hydraulic unit errors", page 58). - 32 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 33: Filling And Draining The Installation

    After the "Commissioning" stage (see page 48), once the machine has started, purge the hydraulic unit again. Precise fi lling pressure is determined by the manometric head of the installation. Loria 6000 R32 / INSTALLATION / 2256 - EN - 33 -...
  • Page 34: Electrical Connections

    3 x 2.5 mm² max. Electrical panel Mains power supply Phase, Neutral, Earth fi g. 35 - Overall layout of the electrical connections for a single installation (1 heating circuit) - 34 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 35: Electrical Power Connections (Lv)

    3 x 2.5 mm² (the spring terminal cannot receive wires Note: The with a diameter exceeding 2.5 mm²). Loria 6000 R32 / INSTALLATION / 2256 - EN - 35 -...
  • Page 36 fi g. 36 - Connections to outdoor unit's terminal block fi g. 37 - Access to outdoor unit's terminal block - 36 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 37 Front Lateral side Back Underneath Devant Côté lateral Derrière Inférieur fi g. 38 - Location of electrical cables and refrigeration connections to outdoor unit (Model 10) Loria 6000 R32 / INSTALLATION / 2256 - EN - 37 -...
  • Page 38 Cable clamp (power) Cable grommet (Sensors) fl exible wire mandatory. Sensor terminal blocks (SELV) Relays HP Controller board Interface board Electric box fi g. 40 - Electric box: Description - 38 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 39 In all cases, please refer to the instruction manuals for the external components (load shedder, etc.) to create the wiring. fi g. 42 - Connection to the terminal board (hydraulic unit) Loria 6000 R32 / INSTALLATION / 2256 - EN - 39 -...
  • Page 40 - Connect the external device to input 7 (External errors - EX3) fi g. - 230 V on input EX3 = heat pump shutdown (the system displays error Er 73). - 40 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 42: Electrical Connections - Selv

    - Connect the outdoor sensor (fi g. 46). fi g. 47 - Outdoor sensor (recommended exposure) - 42 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 43 Connect the room thermostat 2 (fi g. 46). ▼ Installing a Typass ATL (option) Connect the Typass ATL to connector (fi g. 49). fi g. 49 - Typass ATL connections Loria 6000 R32 / INSTALLATION / 2256 - EN - 43 -...
  • Page 44: Controller Interface

    - Display: see § "Display Description", page 45 - View the settings. Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). - 44 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 45: Display Description

    - programme set on the room thermostat Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). Loria 6000 R32 / INSTALLATION / 2256 - EN - 45 -...
  • Page 46: Temperature Control

    This operating mode provides better thermal comfort. *depending on option - 46 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 47 & No correction Cold Cold & No correction & No correction Cold & No correction & & Cold fi g. 52 - Corrective actions in case of discomfort Loria 6000 R32 / INSTALLATION / 2256 - EN - 47 -...
  • Page 48: Commissioning

    17°C, the electrical back-up is automatically activated. Manual manoeuvre: opens all the channels for fi lling and/or drainage. fi g. 53 - Distribution valve (optional DHW kit) - 48 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 49: Cleaning The Fi Lter Valve

    fl oor heating system (parameter "88" & "89", page 54). The parameter must be set to "Off " to deactivate the fl oor drying mode. Loria 6000 R32 / INSTALLATION / 2256 - EN - 49 -...
  • Page 50: Controller Menu

    53 (CC2) installation - see page 43). 35 (CC1) Emitter type 55 (CC2) System with underfl oor heating, ensure that the underfl oor heating safety device is connected. - 50 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 51: List Of Parameters

    DHW back-up prohibited 0 (no)... 1 (yes) Software version 0... 99 Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). Loria 6000 R32 / INSTALLATION / 2256 - EN - 51 -...
  • Page 52 Min. initial cooling setpoint 5... 30 °C 10 °C Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). - 52 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 53 When the function is activated, the Legionella cycles take place on Friday at 3 a.m. Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). Loria 6000 R32 / INSTALLATION / 2256 - EN - 53 -...
  • Page 54 Zone 2 tile drying 2 (Mode 2) 3 (Mode 3) Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). - 54 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 55 00:15... 24:00 Outdoor temperature limit - silent mode -15...30°C 5°C Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). Loria 6000 R32 / INSTALLATION / 2256 - EN - 55 -...
  • Page 56: Displaying Information

    DHW - Energy consumed this month ... kWh DHW - Energy consumed last month ... kWh DHW - Energy consumed this year ... MWh DHW - Energy consumed last year ... MWh - 56 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 57 Frost protection activated. Floor drying mode. Rate input activated. Value... DHW status Pending. Comfort mode, charge activated. Reduced mode, charge activated Legionella charge. Frost protection activated. Forced operation. (boost) Loria 6000 R32 / INSTALLATION / 2256 - EN - 57 -...
  • Page 58: Troubleshooting

    Stored energy: after cutting off the power supplies, wait for 10 minutes before accessing the internal parts of the equipment. Frost protection is not available when the heat pump is not powered up. - 58 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 59 Stored energy: after cutting off the power supplies, wait for 10 minutes before accessing the internal parts of the equipment. Frost protection is not available when the heat pump is not powered up. Loria 6000 R32 / INSTALLATION / 2256 - EN - 59 -...
  • Page 60: Outdoor Unit Errors

    Stored energy: after cutting off the power supplies, wait for 10 minutes before accessing the internal parts of the equipment. Frost protection is not available when the heat pump is not powered up. - 60 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 61 Ο ● Discharge temperature protection Ο Ο Ο ● Compressor temperature protection Ο Ο Ο ● Low pressure abnormal Ο Ο ● ● Outdoor unit radiator temperature error Loria 6000 R32 / INSTALLATION / 2256 - EN - 61 -...
  • Page 62: Safety Thermostat

    Remove the expansion vessel (fi g. 56) and reset when the water temperature has returned to normal. fi g. 54 - Reset button (overheating safety device) - 62 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 64: Maintaining The Installation

    If the installation is fi tted with a DHW tank: - Verify the safety unit on the cold water supply inlet. - Run it according to the manufacturer's instructions. - Check the disconnector. - 64 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 65: Maintenance

    Bleed tap the supply bundle (see page 74). vidange Fuse properties: - T3.15AH250V, 5x20 mm, IEC 60127-1, fi g. 57 - Bleed tap - T6.3AH250V, 5x20 mm, IEC 60127-1. Loria 6000 R32 / INSTALLATION / 2256 - EN - 65 -...
  • Page 66: Appendices

    15°C < T d) Repeat this operation at least three times. Pmax - bar 0.009 0.015 0.020 Remember: performing these operations using - mbar refrigerant is strictly prohibited. - 66 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 67 (4mm) Orifice de charge Filling hole Plug (B) Bouchon (B) High-pressure hose (red) Flexible haute pression (rouge) fi g. 58 - Connecting the hose to the gas valve Loria 6000 R32 / INSTALLATION / 2256 - EN - 67 -...
  • Page 68: Overall Hydraulic Layout

    ► Overall hydraulic layout Installation confi guration - see page 51 Parameter 4 - 1 (1 heating circuit) - 68 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 69 Installation confi guration - see page 51 Parameter 4 - 3 (2 heating circuits with decoupling cylinder) Loria 6000 R32 / INSTALLATION / 2256 - EN - 69 -...
  • Page 70 Installation confi guration - see page 51 Parameter 4 - 1 (1 heating circuit) Parameter 5 - 1 (DHW tank) - 70 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 71 Installation confi guration - see page 51 Parameter 4 - 3 (2 heating circuits with decoupling cylinder) Parameter 5 - 1 (DHW tank) Loria 6000 R32 / INSTALLATION / 2256 - EN - 71 -...
  • Page 72: Electrical Wiring Diagrams

    GN Green GY Grey OG Orange RD Red VT Violet WH White YE Yellow fi g. 59 - Electrical wiring of the outdoor unit models 4, 6 and 8 - 72 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 73 Electricity supply 230 Interconnexion Alimentation between outdoor unit Unité extérieure / électrique (230V) and hydraulic unit Module hydraulique fi g. 60 - Electrical wiring of the outdoor unit model 10 Loria 6000 R32 / INSTALLATION / 2256 - EN - 73 -...
  • Page 74 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 3 2 1 4 3 2 1 3 2 1 CN18 - 74 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 75 Relais appoint chauffage / Heating back-up relay Heating back-up relay Options Options Fuse specifi cations Caractéristiques fusibles T3.15AH250V, 5x20 mm, IEC 60127-1 Fuse specifications T6.3AH250V, 5x20 mm, IEC 60127-1 Loria 6000 R32 / INSTALLATION / 2256 - EN - 75 -...
  • Page 76: Quick-Start Procedure

    Connection to outdoor unit (L, N, Earth). Sensors connection (positioning and connections). Distribution valve connections (boiler and DHW) and circulation pump. Power supply and protection of electric backup (option). - 76 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 77 Explanations of use The heat pump is ready for operation ! Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). Loria 6000 R32 / INSTALLATION / 2256 - EN - 77 -...
  • Page 78: Settings Sheet

    Domestic hot water ► Start-up data sheet Legionella cycle Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). - 78 - Loria 6000 R32 / INSTALLATION / 2256 - EN...
  • Page 79 Also explain to the user how to check the fi lling of the contact you installer or the local representative in order heating circuit. to proceed with the dismantling and recycling of this apparatus. Loria 6000 R32 / INSTALLATION / 2256 - EN - 79 -...
  • Page 80 Date de la mise en service : www.atlantic.fr Société Industrielle de Chauffage Coordonnées de votre installateur chauffagiste ou service après-vente. SATC - BP 64 - 59660 MERVILLE - FRANCE This appliance marked with this symbol. means that electrical electronic products...