INSTALLATION Loria Duo 6000 R32 Air/water heat pump split, 2 services Outdoor unit WOYA060KLT WOYA080KLT WOYA100KLT Hydraulic unit 023017 023018 023019 024159 U0710290_2257_EN_1 For professionals 20/09/2021 To be kept by the user for future reference...
Page 2
■ Installation and maintenance rules loosened with bare hands). If this is not the case, tighten them using a C spanner. The appliance must be installed and maintained - Check also that the refrigeration connections are by an approved professional in accordance with sealed (plastic caps or tubes crimped at the ends the prevailing regulations and code of practice, in and brazed).
Page 3
■ Characteristics of the electrical power supply • Connecting to screw terminals Use of ring terminals or tips is prohibited. Always check that the electric power supply is switched off before works. - Always choose a rigid wire that complies with current standards.
Page 5
Important information that must always be kept in Warning : Slightly fl ammable refrigerant. mind. Tips and advice Read the installation manual Bad practice Read the operating manual Read the installation and operating manuals Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 5 -...
The acoustic power is a measurement made in the laboratory of the power of refrigerant lines. the noise emitted but contrary to the noise level, it does not correspond to the measurement of what is felt. Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 7 -...
Page 8
Overhead view Vue de dessus Vue de dessus Dimensions of the hydraulic unit, see § page 20 fi g. 1 - Dimensions of the hydraulic unit in mm - 8 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 9
■ Outdoor Unit, models 3, 4 , 6 ■ Outdoor Unit, model 8 ■ Outdoor Unit, model 10 fi g. 2 - Dimensions of the outdoor unit in mm Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 9 -...
Page 10
-20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 Temperature °C fi g. 3 - Ohmic value of the sensors (outdoor unit) - 10 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
PAC -Heat pump Ev - Evaporator Cp - Compressor Cn - Condenser Dt - Expansion valve fi g. 8 - Operating principle of a heat pump - 14 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 15
To ensure that the DHW setpoint is reached, the electrical back-up system must be left on. Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 15 -...
fi g. 11 - Open the outdoor unit model 10 Poignées handles fi g. 9 - Recommended example of refrigerant connections layout fi g. 12 - Transport of the outdoor unit model 10 - 16 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
L = 200 mm max 500 mm M = 300 mm max fi g. 13 - Minimum installation clearances around the outdoor unit (model 3, 4 , 6 & 8) Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 17 -...
Page 18
M = 300 mm max 500 mm N = 500 mm max 600 mm fi g. 14 - Minimum installation clearances around the outdoor unit (model 10 ) - 18 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 19
Trace heating must heat not only the drain pipe but also the bottom of the appliance's condensate collection tank. fi g. 15 - Positioning the outdoor unit, discharging condensates Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 19 -...
fi nal connection, take care to put the caps back in position to avoid any pollution of the refrigeration circuit (sealing with adhesive is prohibited). - 20 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 21
fi g. 17 - Removing the front panel fi g. 18 - Floor fi xing Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 21 -...
Page 22
1220 1270 1730 charge 25 m min room volume R32 gas 1345 1395 1830 charge 30 m min room volume fi g. 19 - Minimum room volume - 22 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 23
1100 600 No requirement 1170 600 1300 700 1400 750 1500 800 1600 850 1700 900 1800 950 1840 950 fi g. 21 - Section of the opening Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 23 -...
Page 24
Minimal section (Smin) of the low opening (cm 1000 No requirement 1100 1170 1300 1400 1500 1600 1700 1800 1840 fi g. 24 - Minimal section of the opening - 24 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 25
See fi g. 24 and fi g. 22 Voir figure xx pxx Ajout d’un détecteur Add a detector and a mechanical ventilation d’une ventilation mécanique fi g. 25 - Min. room surface Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 25 -...
Do not use mineral oil. • Brazing the refrigeration circuit (if necessary) - Silver brazing (40% minimum recommended). - Brazing only with dry nitrogen internal fl ux. - 26 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
- Restart the commissioning procedure. Liaison connection Azote Nitrogen Liquid Liaison connection liquide Azote Nitrogen fi g. 29 - Checking refrigeration connections fi g. 30 - Additional fi lling label Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 29 -...
Page 30
(set of pressure gauges). Always fi ll in the liquid phase. Never exceed maximum length diff erence in level. Liquid fi g. 31 - Gas bottle R32 - 30 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 31
"gas" and "liquid" valves. After 2 to 3 minutes repeat fi g. 32 - Location of DIP switches and LEDs on the pump down operation. the hydraulic unit interface board Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 31 -...
(HC2) Buff er on HC1 UFH-R DynR or FC return DynR or FC Radiators Buff er on return of 2 circuits DynR or FC DynR or FC - 32 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
There should be no valve between the safety unit and the tank. We recommend that a thermostatic mixer be placed on the hot water outlet. Filling and draining the installation See § " Commissioning", page 48 Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 33 -...
Mains power supply Phase, Neutral, Earth (see table below) fi g. 36 - Overall layout of the electrical connections for a single installation (1 heating circuit) - 34 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Note: The cable used to connect the electrical back-up must not exceed 3 x 2.5 mm² (the spring terminal cannot receive wires with a diameter exceeding 2.5 mm²). Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 35 -...
Page 36
fi g. 37 - Connections to outdoor unit's terminal block fi g. 38 - Access to outdoor unit's terminal block - 36 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 37
Front Lateral side Back Underneath Devant Côté lateral Derrière Inférieur fi g. 39 - Location of electrical cables and refrigeration connections to outdoor unit (Model 10 ) Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 37 -...
- Connect the outdoor sensor (fi g. 45). fi g. 46 - Outdoor sensor (recommended exposure) - 42 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 43
Connect the room thermostat 2 (fi g. 45). ▼ Installing a Typass ATL (option) Connect the Typass ATL to connector (fi g. 48). fi g. 48 - Installation du Typass ATL Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 43 -...
- Display: see Display Description - View the settings. These parameters (or menus) may not appear. They depend on the appliance's confi guration (on the options selected). - 44 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
- programme set on the room thermostat These parameters (or menus) may not appear. They depend on the appliance's confi guration (on the options selected). Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 45 -...
This operating mode provides better thermal comfort. * On the options selected - 46 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 47
No correction Cold Cold & No correction & No correction Cold & No correction & & Cold fi g. 51 - Corrective actions in case of discomfort Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 47 -...
Note: When starting up the heating function after the HP has been fully shut down and for a heating network temperature not exceeding 17°C, the electrical back-up is automatically activated. - 48 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
The pump is shut down for a few minutes only, before trying again. - If the problem persists, Er 131 is displayed. The appliance then becomes locked: press "OK" to restart the appliance. Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 49 -...
* System with underfl oor heating, ensure that the underfl oor heating safety device is connected. Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). - 50 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
0 (no)... 1 (yes) Software version 0... 99 Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 51 -...
Page 52
Min. initial cooling setpoint 5... 30 °C 10 °C Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). - 52 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 53
Correction of outdoor temperature sensor - 5... 5 °C Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 53 -...
Page 54
3-way valve position during manual mode 0 (heating)... 1 (DHW) Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). - 54 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 55
Outdoor temperature limit - attenuation mode -15...30°C 5°C Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 55 -...
DHW - Energy consumed last year ... MWh Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). - 56 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 57
Legionella charge. Frost protection activated. Forced operation. (boost) Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 57 -...
Stored energy: after cutting off the power supplies, wait for 10 minutes before accessing the internal parts of the equipment. Frost protection is not available when the heat pump is not powered up. - 58 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 59
Stored energy: after cutting off the power supplies, wait for 10 minutes before accessing the internal parts of the equipment. Frost protection is not available when the heat pump is not powered up. Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 59 -...
Stored energy: after cutting off the power supplies, wait for 10 minutes before accessing the internal parts of the equipment. Frost protection is not available when the heat pump is not powered up. - 60 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 61
Compressor temperature protection Ο Ο Ο ● Low pressure abnormal Ο Ο ● ● Outdoor unit radiator temperature error : LED Off ; ● : LED on Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 61 -...
Remove the front panel (fi g. 17, page 21) and reset when the water temperature has returned to normal. fi g. 53 - Reset button (overheating safety device) - 62 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
- Verify the safety unit on the cold water supply inlet. - Run it according to the manufacturer's instructions. - Check the disconnector. fi g. 54 - Reset button (overheating safety device) - 64 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
• Checking the refrigeration circuit - Check that there are no leaks (connectors, valves, etc.). fi g. 55 - Draining of the hydraulic unit and/or hot water tank Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 65 -...
- Open the drainage valve (ref. 5). - Open the hydraulic unit’s automatic bleeders (ref. 6). fi g. 57 - Electric box: Description - Open the installation's air bleeder. - 66 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
15°C < T d) Repeat this operation at least three times. Pmax - bar 0.009 0.015 0.020 Remember: performing these operations using - mbar refrigerant is strictly prohibited. - 68 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 69
Orifice de charge Filling hole Plug (B) Bouchon (B) High-pressure hose (red) Flexible haute pression (rouge) fi g. 58 - Connecting the hose to the gas valve Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 69 -...
GY Grey OG Orange RD Red VT Violet WH White YE Yellow fi g. 59 - Outdoor unit electrical cabling models 3, 4 , 6 and 8 - 72 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 73
Electricity supply 230 Interconnexion Alimentation between outdoor unit Unité extérieure / électrique (230V) and hydraulic unit Module hydraulique fi g. 60 - Outdoor unit electrical cabling model 10 Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 73 -...
Page 74
2nd Circuit sensor Caractéristiques fusibles T3.15AH250V, 5x20 mm, IEC 60127-1 According to confi guration Selon configuration Fuse specifi cations Fuse specifications T6.3AH250V, 5x20 mm, IEC 60127-1 According to configuration - 74 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Connection to outdoor unit (L, N, Earth). Sensors connection (positioning and connections). Distribution valve connections (DHW) and circulation pump. Power supply and protection of electric backup (option). - 76 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Page 77
Control (see chapters " Controller Interface", page 44 " Controller Menu", page Settings, maintenance, checks. Setpoint display. Explanations of use The heat pump is ready for operation ! Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 77 -...
Errors (see page Outdoor unit errors (see page Some settings (or menus) might not be displayed. They are dependent on the installation's confi guration (and installed options). - 78 - Loria Duo 6000 R32 / INSTALLATION / 2257 - EN...
Also explain to the user how to check the fi lling of the contact you installer or the local representative in order heating circuit. to proceed with the dismantling and recycling of this apparatus. Loria Duo 6000 R32 / INSTALLATION / 2257 - EN - 79 -...