alféa S excellia Document n° 1363-5 ~ 06/09/2010 3-phase Heat pump air/water split single service 3-phase model S 11 excellia 3-phase model S 14 excellia 3-phase model S 16 excellia 3-phase Installation and operating manual intended for professionals To be saved for future consultation w w w .
Heat pump alféa S excellia 3-phase Contents Description of the unit ......5 Package .
Page 3
Heat pump alféa S excellia 3-phase Regulation system ....... 29 User interface and room control unit (option) .
Page 4
Heat pump alféa S excellia 3-phase " This device requires for its installation, the intervention of qualified personnel with a certificate of capacity for handling refrigerants. Packing list Heat pump Outdoor unit Hydraulic unit Model Model Code Model Code alféa S11 excellia 3-phase 522634 WOYK112LAT 700110...
Heat pump alféa S excellia 3-phase 1 Description of the unit Definitions Package Split : The heat pump consists of two elements • 1 package : Outdoor unit. (an outdoor unit for outside and a hydraulic unit for • 1 package : Hydraulic unit and outdoor sensor. inside the dwelling).
Heat pump alféa S excellia 3-phase Heating power curve Values according to standard EN 14511, for which it is necessary to add the power absorbed by the heating circulation pump . S 11 Floor heating system (35°C) Low temperature radiator (45°C) Classic radiator (60°C) Heat output Power absorbed Outside temperature (°C) S 14 Floor heating system (35°C) Low temperature radiator (45°C) Classic radiator (60°C) Heat output Power absorbed Outside temperature (°C) S 16 Floor heating system (35°C) Low temperature radiator (45°C) Classic radiator (60°C) Heat output Power absorbed...
Heat pump alféa S excellia 3-phase Operating principle • Domestic hot water (DHW) operating principle The heat pump transmits the energy contained in the surrounding air into the dwelling to be heated. Two domestic hot water (DHW) temperatures can be parametered: comfort temperature (line 1610 to 50 °C) The heat pump consists of four main elements, in which and reduced temperature (line 1612 to 25 °C).
Heat pump alféa S excellia 3-phase 2 Installation Regulation installation 2.2.3 Accessories provided and maintenance conditions - Accessories provided with the outdoor unit (figure 10). The appliance must be installed and the maintained by an - Accessories provided with hydraulic unit approved professional in accordance with the prevailing (figure...
Page 13
Heat pump alféa S excellia 3-phase • Water may drain away from the outdoor unit when it • Make sure the appliance not disturb the surrounding is operating. Do not install the appliance on a paved area or users (noise level, draught generated, low terrace ;...
Heat pump alféa S excellia 3-phase 2.4.2 Outdoor unit positioning The outdoor unit must be raised at least 50 mm above ground level. In areas prone to snow, this height should be increased but should not exceed 1,5 m (figure 12).
Heat pump alféa S excellia 3-phase Installing the hydraulic unit 2.5.2 Positioning the hydraulic unit - Remove the front panel (2 screws A, figure 2.5.1 Installation precautions - Remove the sides (4 screws B, figure 15). • The room in which the appliance operates must comply - Fix the support solidly (3 screws and plugs) to a flat, with the prevailing regulations.
Heat pump alféa S excellia 3-phase Refrigeration connections • To eliminate any filings in the pipes, use dry nitrogen to avoid introducing any humidity that may adversely " This appliance uses refrigerant R410A. affect the appliances operation. In general, take every Comply with the legislation for handling refrigerants.
Heat pump alféa S excellia 3-phase 2.6.3 Creating the flarings 2.6.4 Shaping the refrigeration pipes - Cut the pipe to an appropriate length with a pipe-cutter The refrigeration pipes must be shaped only on a without deforming it. bending machine or with a bending spring in order to avoid any risk of crushing or breaking them.
Page 18
Heat pump alféa S excellia 3-phase Diameter of refrigeration Outdoor unit connections Hydraulic unit connections connections 5/8" (D1) 5/8" 5/8" Liquid 3/8" (D2) 3/8" 3/8" Liquid valve Gas valve Flare nut Liquid refrigeration connection diameter D2 Flare nut Flare nut Flare nut Gas refrigeration connection diameter D1...
Heat pump alféa S excellia 3-phase Filling the installation with gas Manomter kit " This operation is reserved for installers familiar (manifold) with the legislation for handling refrigerants. " Creating a vacuum with a vacuum pump is High pressure pressure essential.
Heat pump alféa S excellia 3-phase 2.7.3 Additional charge 50 g of R410A per additional meter Length of the connections 15 m 20 m Additional charge none 250 g 2.7.4 Pump down The charge in the outdoor units corresponds to the (Refrigerant collecting operation) maximum distances between the outdoor unit and the hydraulic unit defined in...
Heat pump alféa S excellia 3-phase Connecting 2.8.2 Rinsing out the installation the heating circuit hydraulically Before connecting the hydraulic unit to the installation, rinse out the heating system correctly to eliminate 2.8.1 General any particles that may affect the appliance’s correct The connection must comply with good trade practice operation.
Heat pump alféa S excellia 3-phase Electrical connections • Connecting to screw terminals Rigid wires (A, figure 27). Ensure that the general electrical power supply has Rigid wires are always preferable for fixed installations, been cut off before starting any repair work. particularly in a building.
Heat pump alféa S excellia 3-phase 2.9.3 Overview of all the electrical connections The wiring diagram for the hydraulic unit is shown in detail on figure 46, page Room control unit radio (option) Outdoor sensor : cable 2 x 0,75 mm² Interconnection between the outdoor unit and the hydraulic unit Phase, neutral, earth, communication...
Heat pump alféa S excellia 3-phase 2.9.5 Electrical connections - Use cable clamps to prevent the conductors from being disconnected accidentally. on the outdoor unit side - Fill in the space where the cables enter the outdoor Access to the connection terminals. unit with the insulating plate.
Heat pump alféa S excellia 3-phase 2.9.6 Electrical connections on the hydraulic unit side Access to the connection terminals. Do not place the sensor lines and the sector supply lines in parallel in order to avoid causing inadvertent - Remove the front panel (2 screws) interference due to voltage points in the sector supply.
Page 26
Heat pump alféa S excellia 3-phase Outdoor unit Hydraulic unit 1 2 3 4 5 6 7 8 20 21 22 23 12 13 14 15 16 17 18 19 RP DHW 1 2 3 L1 L2 L3 N N COM OUTDOOR SECOND ELECTRIC...
Heat pump alféa S excellia 3-phase Outdoor sensor Room thermostat circuit 1 Room thermostat circuit 2 External fault Tariffs, day / night, peak times/off-peak times Power shedding Room control unit or EJP (peak day removal) Room control unit radio T78 External component contact* (faults, load shedder, power meter) * If the control device does not provide a potential-free contact, the contact must be relayed to create equivalent wiring.
Heat pump alféa S excellia 3-phase 2.12 Start-up 2.13 Configuring the room thermostat - Make sure that ALL DIP SW are OFF before starting To configure the room thermostat and connect it to the up. DIP SW shuold be set OFF for normal operation. appropriate heating zone : Power supply to the hydraulic unit must be turned off - Hold down the presence key for more than 3 seconds.
Heat pump alféa S excellia 3-phase 3 Regulation system User interface and room control unit (option) Auto Auto Figure 39 - RESET Ref. Function - Definitions Selecting of the DHW operating mode - If the installation is fitted with a DHW tank. (Domestic hot water).
Heat pump alféa S excellia 3-phase Room thermostat (option) Auto °C Figure 40 - Room thermostat (option) Ref. Function - Definitions Selecting the heating mode. Auto Heating operating according to the heating programme (Summer/winter mode switchover is automatic). Constant comfort temperature. Constant reduced temperature.
Page 31
Heat pump alféa S excellia 3-phase Heating curve slope 2,75 ° C 2,25 Classic temperature radiator 1,75 Boiler connection application 1,25 Heat pump application only temperature radiator 0,75 Floor heating system 0,25 ° C Outdoor temperature °C Figure 41 - Heating curve slope (line 720) Heating curve slope +4,5 -4,5...
Heat pump alféa S excellia 3-phase Parametering the setting 3.4.2 Setting parameters - Choose the desired level. 3.4.1 General - Scroll the menu list. Only the parameters accessible to levels : - Choose the desired menu. U - End user. - Scroll the function lines.
Page 33
Heat pump alféa S excellia 3-phase Setting range Setting Basic Line Function or display increment setting Operation HCP (domestic hot water pump command, output QX2) Commonly with Commonly with HC1 or Independent (if independent, see timer program 3 / HCP) Software version (Display) Heating time programme, circuit 1 Pre-selection (Day / Week)
Page 34
Heat pump alféa S excellia 3-phase Setting range Setting Basic Line Function or display increment setting Time programme 5 / Cooling If the installation is fitted with the cooling kit (Only with the cooling kit option). Pre-selection (Day / Week) Mon-Sun Mon-Sun Mon-Fri Sat-Sun Monday Tuesday…...
Page 35
Heat pump alféa S excellia 3-phase Setting range Setting Basic Line Function or display increment setting Flow temp setpoint max 8... 95 °C 1 °C 55 °C Floor heating system = 50 °C / Higher temperature radiator = 65 °C Room influence 1%...
Page 36
Heat pump alféa S excellia 3-phase Setting range Setting Basic Line Function or display increment setting Cooling circuit 1 Operating mode Off, Automatic Comfort cooling setpoint 17... 40 °C 0,5 °C 24 °C Release 24h/day, Time program HC, Time Time program 5 / Refresh program 5 If the installation is fitted with a DHW tank, set the parameter 907 to "...
Page 37
Heat pump alféa S excellia 3-phase Setting range Setting Basic Line Function or display increment setting 1030 Summer / Winter heating limits 8... 30 °C 0,5 °C 18 °C When the average of the outdoor temperatures over the past 24 hours reaches 18°C, the regulator switches off the heating (as an economy measure).
Page 38
Heat pump alféa S excellia 3-phase Setting range Setting Basic Line Function or display increment setting 1620 Release (of DHW load) 24h / day Time program Time programs HCs 4/DHW Time program 4/DHW Low-tariff T'prog 4/DHW or low-tariff 24h / day : The temperature of the DHW is constantly maintained at the DHW comfort setting. Time programs HCs : The DHW is produced according to the programming for the ambient temperature (with 1 hour in advance when switched on).
Page 39
Heat pump alféa S excellia 3-phase Setting range Setting Basic Line Function or display increment setting Domestic hot water (DHW) (Only with the DHW kit option) 5020 Flow setpoint boost 0... 30 °C 1 °C 5 °C 5024 Switching diff 0...
Page 40
Heat pump alféa S excellia 3-phase Setting range Setting Basic Line Function or display increment setting 6800 History 1 Time, Date, Error code 6802 History 2 Time, Date, Error code 6804 History 3 Time, Date, Error code 6806 History 4 Time, Date, Error code 6808 History 5...
Page 41
Heat pump alféa S excellia 3-phase Setting range Setting Basic Line Function or display increment setting 7710 Output (Ux) test --, 0... 100% 7711 Voltage (Ux) value 0... 10 Volt 7720 Digital outputs test No test 0 = No test 1 = Everything is on STOP 2 = Digital output DO1 3 = Digital output DO2...
Page 42
Heat pump alféa S excellia 3-phase Setting range Setting Basic Line Function or display increment setting Diagnostics heat generation 8402 Electrical resistance flow 1 Off, On 8403 Electrical resistance flow 2 Off, On 8406 Condenser pump Off, On 8410 Return temp HP 0...
Page 43
Heat pump alféa S excellia 3-phase Setting range Setting Basic Line Function or display increment setting 8770 Room temperature 2 0... 50 °C 20 °C Room setpoint 2 4... 35 °C 20 °C 8773 Flow temperature 2 0... 140 °C 50 °C Flow temperature setpoint 2 0...
Heat pump alféa S excellia 3-phase 4 Configuring the installation " Optional DHW kit " Optional boiler connection kit DHW tank control (with electrical back-up) requires the The connection of an oil or gas boiler to the heat pump use of the DHW kit. requires the installation of the boiler connection kit.
Heat pump alféa S excellia 3-phase Configuration 1, 2, 3 or 4: heat pumps with electric back-ups " Parameter 5700. Configuration 1 : 1 heating circuit (see figure page 45). Configuration 2 : 1 heating circuit and DHW tank. (see figure page 46).
Page 46
Heat pump alféa S excellia 3-phase Configuration 1 : " See detailed instructions 1 heating circuit. page 44. Overall hydraulic layout Overview of all the electrical connections Legend CC - Heating circulation pump. R - Radiators (or fan convectors). SA - Room thermostat (option). SE - Outdoor sensor.
Page 47
Heat pump alféa S excellia 3-phase Configuration 2 : " See detailed instructions 1 heating circuit and DHW tank. page 44. Overall hydraulic layout Overview of all the electrical connections Legend CAR - Non-return valve. SA - Room thermostat (option). AE - Electric back-up.
Page 48
Heat pump alféa S excellia 3-phase Configuration 3 : " See detailed instructions 2 heating circuits. page 44. Overall hydraulic layout SDp1 Overview of all the electrical connections SDp1 Legend R - Radiators (or fan convectors). SP - Heated floor thermal safety fuse. CAR - Non-return valve.
Page 49
Heat pump alféa S excellia 3-phase Configuration 4 : " See detailed instructions 2 heating circuits and DHW tank. page 44. Overall hydraulic layout SDp1 Overview of all the electrical connections SDp1 Legend SE - Outdoor sensor. KS - DHW kit. SDp1 - Flow sensor, Circuit 1.
Heat pump alféa S excellia 3-phase 6 Troubleshooting Depending on whether the fault comes from the outdoor unit or the hydraulic unit, the fault may be indicated by the digital display or the diode on the interface cards. Designation Line Information display Floor drying current setpoint .
Heat pump alféa S excellia 3-phase Faults displayed on hydraulic unit Faults or breakdowns on the hydraulic mode are The display shows the “Bell” symbol indicated by the display on the user interface. Press the Info key for more details on the origin of the fault.
Heat pump alféa S excellia 3-phase Faults displayed on the outdoor unit When an error occurs : To access the electronic board, you must remove the front (right-hand) facing from the outdoor unit. - The diode "ERROR" (2) blinks. Faults are coded by diode flashes. •...
Heat pump alféa S excellia 3-phase 7 Quick-start procedure Before switching on the hydraulic unit : • Check the electric wiring. • Check the refrigeration circuit and make sure the gas supply has been performed. • Check the pressure of the hydraulic circuit (1-2 bar), check that the heat pump is purged, and the rest of the installation.
Heat pump alféa S excellia 3-phase Start-up - Turn ON the start/stop switch. - Time, Date and time programs for HC1, HC2, DHW if different than default values (settings 500 – 576). - Configure the hydraulic circuit (setting 5700) : - Ajust the heating curve slope (720;...
Heat pump alféa S excellia 3-phase Settings sheet Setting Description Set to. Menus Setting Description Set to. Menus Boiler backup Preliminary settings 3700 OT .switch-on authoris . addit. gen. language operator section 3705 swith-off delay addit. gen. hour / minutes time & date Miscellaneous day / month time &...
Heat pump alféa S excellia 3-phase Start-up data sheet Site Installer serial No. serial No. Outdoor unit Hydraulic unit model model Refrigerant type Refrigerant charge Checks Operating voltage & current on outdoor unit Compliance with positioning distances L1/N Condensate evacuation correct L2/N Electric connections / connections tightnees L3/N No GAS leaks (unit ID No . : ) L1/E Installation of refrigeration connection correct (lenght : m) L2/E...
Heat pump alféa S excellia 3-phase 8 Instructions for the user Explain to the user how his installation operates, in Emphasise that a heated floor has significant inertia particular the functions of the room thermostat and the and that therefore any adjustments must be made programmes accessible to him from the user interface.