AXIS A1610 Network Door Controller
Specifications
Select which protocol to use in the product's web page.
Configured for RS485
Function
DC ground (GND)
DC output (+12 V)
RX/TX
TX
Configurable (Input or Output)
Important
• When the reader is powered by the controller, the qualified cable length is up to 200 m (656 ft).
• When the reader is not powered by the controller, the qualified cable length for reader data is up to 1000 m (3280,8 ft) if
the following cable requirements are met: 1 twisted pair with shield, AWG 20-16.
Configured for Wiegand
Function
DC ground (GND)
DC output (+12 V)
D0
D1
O
Configurable (Input or Output)
Pin
1
2
3–4
5–6
7–8
Pin
1
2
3
4
5–6
7–8
Note
Supplies power to reader.
Full duplex: RX. Half duplex:
RX/TX.
Full duplex: TX.
Digital input — Connect to pin
1 to activate, or leave floating
(unconnected) to deactivate.
Digital output — If used with
an inductive load, e.g., a relay,
connect a diode in parallel
with the load, to protect
against voltage transients.
Note
Supplies power to reader.
Digital output, open drain
Digital input — Connect to pin
1 to activate, or leave floating
(unconnected) to deactivate.
Digital output — If used with
an inductive load, e.g., a relay,
connect a diode in parallel
with the load, to protect
against voltage transients.
22
Specifications
0 V DC
12 V DC, max
486 mA combined for all
readers
0 to max 30 V DC
0 to max 30 V DC, open drain,
100 mA
Specifications
0 V DC
12 V DC, max
486 mA combined for all
readers
0 to max 30 V DC
0 to max 30 V DC, open drain,
100 mA